APPENDIX C - Loading a PLC Program
Part No. 750-386
C-3
10. Install the SD card into the PLC SD card slot. The PLC switch should be in REM.
11.Cycle power to the PLC.
12.The transfer from the SD card to the PLC processor will begin. Please be
patient while the installation is in progress, the whole process from power up
to completion may take up to 3 Minutes. Prematurely ending the SD card load
process
may render the PLC unusable!
13.During the transfer process the OK Led on the PLC will be solid RED. The
SD Led will begin to flash GREEN indicating that the PLC is reading from the
SD card. Upon completion, the RUN and OK Led's should be solid GREEN. If
run Led is NOT Solid Green put PLC switch to RUN.
14.Remove the SD card from the PLC SD card slot.
15.If the SD card has come from the factory or if the program was taken from
the CB Portal, loading from the SD card will install PLC firmware, the PLC
program, and set the IP address of the PLC to 192.168.1.150.