Wiring inputs and outputs
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
39
5
Set each output's two DIP switches to the appropriate settings for the type of device wired to the output.
For...
DIP switch on the...
Set to...
Analog 0-20 mA
Top
Up
Bottom
Up
Analog 0-10 Vdc
Top
Up
Bottom
Down
Binary
Top
Down
Bottom
N/A
CAUTION
Outputs are set to Binary in the factory. To avoid damage to the controller, use a voltmeter to
verify there is no voltage on the + and
–
terminals before setting the DIP switch to Analog.
6
Turn
on
the TV-MPCXP1628-NR's power.
See
Troubleshooting inputs and outputs
(page 74).