Wiring inputs and outputs
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
38
4
Connect binary and analog output wiring to the
UO
screw terminals on the TV-MPCXP1628-NR and to the
controlled device. Connect the ground wire to the UO's
–
terminal.
WARNING
Do not apply voltage to any output whose DIP switch is set to Analog.
Any UO
24 Vac/Vdc
+
+
–
–
Gnd
0-10 V
0-10 V
0-20 mA
0-20 mA
Hot
Hot
Gnd
4-wire
3-wire
+
Any UO
+
–
Hot
3-wire
+
Any UO
+
Coil: 24 Vac/Vdc, 1 A max.
Any UO
Analog outputs
Binary outputs
-
-
-
-
-
+
+
–
Hot
Gnd
4-wire
Any UO
+
+
–
0-10 V
2-wire
Any UO
24 Vac/Vdc
+
Any UO
-
-
+
Gnd
24 Vac/Vdc
To external device
24 Vac/Vdc, 1A max.