Wiring for communications
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
26
The TV-MPCXP1628-NR communicates on the following ports.
Port
Protocol
1
Port type(s)
Speed(s)
Gig-E
BACnet/IP
2
BACnet/Ethernet
2
Modbus TCP/IP
Ethernet
10, 100, or 1000 Mbps
(1 Gbps)
Port S1
1
BACnet/ARCNET
BACnet/MSTP
Modbus Serial
RS485
156 kbps
9.6 to 115.2 kbps
4
9.6 to 115.2 kbps
4
Port S2
Modbus Serial
RS485
9.6 to 115.2 kbps
4
Service Port
5
HTTP/IP
Ethernet
10 Mbps
100 Mbps
USB Port
USB2.0
USB
Rnet Port
See
Wiring devices to the TV-MPCXP1628-NR's Rnet port
(page 30).
I/O Bus Port
See
To attach TruVu™ MPC I/O expanders
(page 9).
1
Only one port can be configured for a BACnet communication type. The Gig-E port can run Modbus
simultaneously with either BACnet/IP or BACnet/Ethernet.
2
Since only one port can be configured for a BACnet communication type, if you use the Gig-E port for BACnet/IP
or BACnet/Ethernet, the
Port S1 Configuration
rotary switch must be set to
0
,
3
, or
4
.
3
Set the
Port S1 Configuration
rotary switch to:
0
if port is not used
1
for MS/TP
2
for ARCNET
3
for Modbus
NOTE
4
is for future use.
4
Default for MS/TP is 76.8 kbps.
Default for Modbus is 38.4 kbps.
5
See
To set up the controller through the Service Port
(page 61).
Wiring for communications