Wiring inputs and outputs
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
35
Wiring specifications
Input wiring
Input
Maximum length
Minimum gauge
Shielding
Thermistor
Dry contact
1000 feet
(305 meters)
22 AWG
Shielded
0
–
5 Vdc
0
–
10 Vdc
1000 feet
(305 meters)
26 AWG
Shielded
0
–
20 mA
3000 feet
(914 meters)
26 AWG
Shielded or
unshielded
RTD
100 feet
(30 meters)
22 AWG
Shielded
NOTES
•
Carrier recommends use of an external current transducer between an RTD and the TV-MPCXP1628-NR to
improve accuracy and resolution.
•
RTD inputs require either sensor calibration or an estimated offset correction for wiring resistance. See
Offset
and Polarity values
(page 43).
Output wiring
To size output wiring, consider the following:
•
Total loop distance from the controller to the controlled device
NOTE
Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
•
Acceptable voltage drop in the wire from the controller to the controlled device
•
Resistance (Ohms) of the chosen wire gauge
•
Maximum current (Amps) the controlled device requires to operate