Addressing the TV-MPCXP1628-NR
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
17
2
Turn off the computer's Wi-Fi if it is on.
3
If your computer uses a static IP address, use the following settings:
○
Address: 169.254.1.x, where x is 2 to 7
○
Subnet Mask: 255.255.255.248
○
Default Gateway: 169.254.1.1
If it uses a DHCP address, leave the address as it is.
4
Open a web browser on the computer.
5
Navigate to http://local.access or http://169.254.1.1 to see the controller setup pages.
See
To set up the controller through the Service Port
(page 61) for general information on using the controller
setup pages.
Rotary switch settings
Rotary switch settings (see example below) are used to determine the following items in your system, so you
should plan carefully before setting the switches.
•
If you use a
Default IP address
, the final octet is the number created by the three rotary switch settings (must
be a unique number from 1 to 253). See
To set the IP address
(page 19).
•
If you autogenerate the following:
Device Instance
, the number is automatically set to a number equal to the ((IP network number x 100) +
rotary switch settings).
BACnet Network Number
for Port S1, the number is automatically set to a number equal to the ((IP network
rotary switch settings) x 10).
Autogenerating is set up through the
controller setup pages
(page 61).
•
The rotary switch settings determine the controller number in the i-Vu® interface.
EXAMPLE
The switches below are set to 125.
CAUTION
Do not leave the rotary switches set at 0 (the factory default). The TV-MPCXP1628-NR cannot be
discovered if the rotary switches are left at 0.