Addressing the TV-MPCXP1628-NR
TruVu™ MPC
Controller (part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
20
To set a default IP address
Default IP addressing assigns the following to the controller:
•
IP address = 192.168.168.
x
where
x
is the setting on the rotary switches in the range from 1 to 253
•
Subnet Mask = 255.255.255.0
•
Default Gateway = 192.168.168.254
1
Set the controller's three rotary switches to a unique address on the network. Set the left rotary switch to the
hundreds digit, the middle switch to the tens digit, and the right switch to the ones digit.
EXAMPLE
The switches below are set to 125.
2
On the controller setup
Ports
tab under
IP Port
, select
Default IP Address
.
3
Click
Save
.
CAUTIONS
•
The Default IP address range is 1 to 253. Setting the rotary switches to 0 will set the Default IP address to 1.
Setting the switches to 255 will set the Default IP to 253. Do not set the switches to 254.
•
If you set the Default IP address on the controller setup
Ports
tab and then change the rotary switches, you
must do one of the following to correct the IP address in the controller:
•
Go to the controller setup
Ports
tab and click the
Update IP Address
.
•
Cycle the controller's power.
You will then need to correct the IP address in the i-Vu® application using
Find Devices
and
Upload All
Content
. See the i-Vu® Help for more information.
NOTE
The default address is an intranet address. Data packets from this address are not routable to the Internet.