Wiring for communications
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
27
Wiring specifications
For...
Use...
Maximum Length
BACnet/IP
Ethernet
CAT5e or higher Ethernet cable
328 feet (100 meters)
MS/TP*
ARCNET*
22 AWG, low-capacitance, twisted, stranded,
shielded copper wire *
2000 feet (610 meters)
*
For details see the
Open Controller Network Wiring Guide
.
WARNING
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
To connect the TV-MPCXP1628-NR to the Ethernet
Connect an Ethernet cable to the Gig-E Ethernet port.
NOTE
Be careful NOT to plug your cable into the Service Port.
NOTE
If your system has controllers on different IP subnets separated by an IP router, you must configure one
controller on each subnet as a BACnet Broadcast Management Device (BBMD). Do not configure more than one
BBMD per subnet as this may cause circular routes. See
To set up BACnet Broadcast Management Devices
(BBMDs)
(page 22).