To communicate locally through the Rnet port
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
69
To set up a Local Access connection in the i-Vu® Pro interface
For the i-Vu® Pro application to communicate with the
Rnet
port, you must do the following:
1
Click
, select
System Options
,
and then select
Connections
.
2
On the
Configure
tab, click
Add
.
3
From the
Type
drop-down list, select
BACnet/Rnet Connection
.
4
Optional: Edit the
Description
.
5
Type the computer's
Port
number that the USB cable is connected to.
NOTE
To find the port number, plug the USB cable into the computer's USB port, then select
Start
>
Control
Panel
>
System
>
Device Manager
>
Ports (Com & LPT)
. The COM port number is beside
Silicon Labs
CP210x USB to UART Bridge
.
6
Set the
Baud
rate to 115200.
7
Click
Accept
.
8
On the
View
tab, select
BACnet/Rnet Connection
, from the drop-down list.
9
Click
Accept
.
10
On the
Configure
tab, select
BACnet/Rnet Connection
, then click
Start
.
NOTE
If an error message appears, make sure the COM port you selected is not in use. For example, PuTTY
may be open and is holding the port open.
11
On the navigation tree, select the controller that you are connected to.
12
Click
and select
Manual Command
.
13
Type
rnet here
in the dialog box, then click
OK
.
14
On the
Properties
page, click
Module Status
. If a Modstat report appears, the i-Vu® application is
communicating with the controller.