To set up autobaud
The TV-MPCXP1628-NR can automatically receive or establish the baud rate on an MS/TP or Modbus serial
network. When you configure a device on the network for autobaud and then power it up, the device detects the
incoming baud rate on the network and sets its baud to match.
Autobaud does not work unless there is a device on the network, whether Carrier or third party, that has the baud
rate already set. You can manually set the baud rate on more than one device, as long as the rate is the same for
every device.
NOTES
•
The received baud rate stays intact during power cycles.
•
We recommend you set the baud rate manually on the router for the network.
MS/TP
MSTP Autobaud
can be configured in either of the following locations:
•
Service Port
controller setup pages >
BACnet
tab >
Port S1
or
•
The i-Vu® interface, on the
Network
tree, select your TV-MPCXP1628-NR and go to
Driver
>
BACnet
Controller Properties
>
MS/TP Configuration
on Port S1. See
BACnet Controller Properties
(page 51).
Modbus
Modbus Serial Autobaud
can be configured in either of the following locations:
•
Service Port
controller setup pages >
Modbus
tab >
Modbus RS-485
>
Port Configuration
or
•
In the i-Vu® interface, on the
Network
tree, select your TV-MPCXP1628-NR >
Driver
>
Communication
Status
>
Modbus Serial
NOTE
See the
Modbus Integration Guide
.
NOTE
If you set
Autobaud
or make other changes in the Service Port controller setup pages, you must upload the
changes to the system database the first time you access the controller in the i-Vu® interface. This preserves
those settings when you download memory or parameters to the controller.