To set up the controller through the Service Port
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
64
BACnet tab
NOTE
The TV-MPCXP1628-NR can be configured for only one BACnet communication type.
On the
BACnet
tab, you can:
•
Choose to run
BACnet Over IP
or
BACnet Over Ethernet
on the
Gig-E
Port.
If you choose
BACnet Over IP
, you can edit the
BACnet UDP Port
.
NOTE
The
Port S1 Configuration
rotary switch must be set to 0, 3, or 4 for these options to be editable.
•
The
Port S1 Configuration
rotary switch must be set to 1 for MSTP or 2 for ARCNET.
•
Enable or disable
MSTP Autobaud
on Port S1. This device will receive its baud rate from the master device
with the fixed baud rate.
•
Set
MS/TP Baud Rate
to a baud rate that all other devices on the MS/TP network are set to.
Modbus tab
If the controller will be used with Modbus devices, see the
Modbus Integration Guide
for information on using this
tab.
Security tab
BACnet Firewall
If your BACnet Firewall configuration in the i-Vu® interface did not include the i-
Vu® server IP address, thus blocking communication with the i-Vu® server, you
can disable the controller's BACnet Firewall on the controller setup
Security
tab.
NOTE
You can enable the BACnet Firewall only in the i-Vu® interface.