3
Power
24 Vac ±15%, 50
–
60 Hz, 100 VA
24 Vdc ±10%, 48 W
I/O expanders
Supports up to 9 TruVu™ MPC I/O expanders
Gig-E port
10/100/1000 BaseT, full duplex, Ethernet port for BACnet/IP and/or
BACnet/Ethernet, or Modbus TCP/IP communication.
Port S1
For communication with either of the following:
•
A BACnet ARCNET network at 156 kbps
•
A BACnet MS/TP network at 9600 to 115200 bps
•
A Modbus serial network at 9600 to 115200 bps
This port's
End of Net?
switch can be set to
Yes
to terminate the network segment.
Port S2
For communication with a Modbus serial network at 9600 to 115200 bps.
This port's
End of Net?
switch can be set to
Yes
to terminate the network segment.
Rnet port
•
Supports Up to 15 ZS wireless and/or ZS sensors, and one Equipment Touch
or Tr
uVu™ ET Display
•
Supports local connection for a laptop running the i-Vu® application
•
Supplies 12 Vdc power less than or equal to 162.5 mA when the TV-
MPCXP1628-NR is powered from an AC source and less than or equal to 262.5
mA when powered by a DC source.
•
NOTE
If the total power required by the sensors on the Rnet exceeds the
power supplied by the Rnet port, use an external power source. The Wireless
Adapter, Equipment Touch, or
TruVu™ ET Display must be powered by an
external power source. See the specifications in each device's Installation and
Start-up Guide to determine the power required.
Act Net port
Supports up to 16 i-Vu® Smart Valves
I/O Bus port
Provides communication for up to 9 wired TruVu™ MPC I/O expanders. See
TruVu™
MPC I/O expander configurations
(page 11).
I/O bus edge connector
6-pin connector that provides communication and power to a directly-connected
TruVu™ MPC I/O expander (DC only).
Service Port
Ethernet port at 10 or 100 Mbps for setting up the controller and troubleshooting
Supports local connection for a laptop running the i-Vu® application
USB port
USB 2.0 host port for device recovery
Universal inputs
28
Inputs are configurable in the control program for 0
–
5 Vdc, 0
–
10 Vdc, 0
–
20 mA,
RTD, thermistor, dry contact, or pulse counter.
Input resolution
16 bit A/D
Input pulse frequency
60 pulses per second. Minimum pulse width (on or off time) required for each
pulse is 8.33 msec.