What
is the TruVu™ MPC Controller (part no. TVMPCXP1628
-NR)?
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
2
Port
Port type
For this type of
communication...
At...
Gig-E
10/100/1000 Mbps Ethernet
BACnet/IP
BACnet/Ethernet
Modbus TCP/IP
10, 100, or 1000 Mbps
(1 Gbps)
S1
High-speed EIA-485 port
BACnet/ARCNET
BACnet/MSTP
Modbus Serial
156 Kbps
9.6 to 115.2 kbps
9.6 to 115.2 kbps
S2
Electrically isolated EIA-485 port
Modbus Serial
9.6 to 115.2 kbps
Service
Port
10/100 Mbps Ethernet
HTTP/IP
BACnet/IP Service Port
10 or 100 Mbps
On the non-routing controller:
•
Only one port can be configured for a BACnet communication type.
•
The Gig-E port can run Modbus simultaneously with either BACnet/IP or BACnet/Ethernet.
The TV-MPCXP1628-NR also has the following ports:
•
I/O Bus port for wired TruVu™ MPC I/O
expanders
•
I/O bus edge connector for directly-
connected TruVu™ MPC I/O expande
rs (DC only)
•
Rnet port for ZS sensors, Wireless Adapter
for wireless sensors, an Equipment Touch, and an TruVu™ ET
Display
•
USB port for recovery
•
Act Net port for i-Vu® Smart Valves
Specifications
Driver
drv_fwex_< version >.driverx
Maximum number of control programs*
999
Maximum number of BACnet objects*
12000
Third-party BACnet integration points
1500
Third-party Modbus integration points
200
* Depends on available memory.