96
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Code
Description
Reset
Delay
Alarm relay
Action
ALG15
Generic low temperature alarms 1 to 5, PLB1
Manual/automatic
Settable
Settable
-
ALG16
Generic low temperature alarms 1 to 5, PLB2
Manual/automatic
Settable
Settable
-
ALG17
Generic low temperature alarms 1 to 5, PLB3
Manual/automatic
Settable
Settable
-
ALG18
Generic low temperature alarms 1 to 5, PLB4
Manual/automatic
Settable
Settable
-
ALG19
Generic high modulation alarms 6 and 7, PLB1
Manual/automatic
Settable
Settable
-
ALG20
Generic high modulation alarms 6 and 7, PLB2
Manual/automatic
Settable
Settable
-
ALG21
Generic high modulation alarms 6 and 7, PLB3
Manual/automatic
Settable
Settable
-
ALG22
Generic high modulation alarms 6 and 7, PLB4
Manual/automatic
Settable
Settable
-
ALG23
Generic low modulation alarms 6 and 7, PLB1
Manual/automatic
Settable
Settable
-
ALG24
Generic low modulation alarms 6 and 7, PLB2
Manual/automatic
Settable
Settable
-
ALG25
Generic low modulation alarms 6 and 7, PLB3
Manual/automatic
Settable
Settable
-
ALG26
Generic low modulation alarms 6 and 7, PLB4
Manual/automatic
Settable
Settable
-
ALG27
Normal alarm generic functions 8/9, PLB1
Manual/automatic
Settable
Settable
-
ALG28
Serious alarm generic functions 8/9, PLB1
Manual/automatic
Settable
Settable
-
ALG29
Normal alarm generic functions 8/9, PLB2
Manual/automatic
Settable
Settable
-
ALG30
Serious alarm generic functions 8/9, PLB2
Manual/automatic
Settable
Settable
-
ALG31
Normal alarm generic functions 8/9, PLB3
Manual/automatic
Settable
Settable
-
ALG32
Serious alarm generic functions 8/9, PLB3
Manual/automatic
Settable
Settable
-
ALG33
Normal alarm generic functions 8/9, PLB4
Manual/automatic
Settable
Settable
-
ALG34
Serious alarm generic functions 8/9, PLB4
Manual/automatic
Settable
Settable
-
ALH01
ChillBooster fault
Automatic
Settable
R2
Disable ChillBooster
ALH02
ChillBooster fault, line 2
Automatic
Settable
R2
Disable ChillBooster
ALO02
pLAN malfunction
Automatic
60s
R1
Shutdown unit
ALT01
Compressor maintenance request
Manual
-
Not featured
-
ALT02
Compressor maintenance request, line 2
Manual
-
Not featured
-
ALT03
ChillBooster maintenance request
manual
0s
Not featured
-
ALT04
ChillBooster maintenance request, line 2
manual
0s
Not featured
-
ALU01
Confi guration not allowed
Automatic
Not featured
Not featured
Shutdown unit
ALU02
Control probes missing
Automatic
Not featured
Not featured
Shutdown unit
ALW01
High pressure prevent warning
Automatic
Settable
Not featured
Shutdown compressor, except mini-
mum load stage
ALW02
High pressure prevent warning, line 2
Automatic
Settable
Not featured
Shutdown compressor line 2, except
minimum load stage
ALW03
Compressor inverter warning
Automatic
Not featured
Not featured
-
ALW04
Compressor inverter warning, line 2
Automatic
Not featured
Not featured
-
ALW05
Fan inverter warning
Automatic
Not featured
Not featured
-
ALW06
Fan inverter warning, line 2
Automatic
Not featured
Not featured
-
ALW07
Envelope warning: refrigerant not compatible with compressor series
Automatic
Not featured
Not featured
-
ALW08
Envelope warning: custom envelope not confi gured
Automatic
Not featured
Not featured
-
ALW09
Envelope warning: suction or condensing probes not confi gured
Automatic
Not featured
Not featured
-
ALW10
Low superheat warning
Automatic
Not featured
Not featured
-
ALW11
Low superheat warning, line 2
Automatic
Not featured
Not featured
-
ALW12
Warning, ChillBooster operating without outside sensor
Automatic
0s
Not featured
-
ALW13
Warning, ChillBooster operating without outside sensor, line 2
Automatic
0s
Not featured
-
ALE01
EEV motor error on Driver 1
Automatic
Confi g.
Confi g.
-
ALE01
High condensing temperature on Driver 1
Automatic
Confi g.
Confi g.
-
ALE01
Low suction temperature on Driver 1
Automatic
Confi g.
Confi g.
-
ALE02
Low superheat on Driver 1
Automatic
Confi g.
Confi g.
-
ALE02
Low operating pressure on Driver 1
Automatic
Confi g.
Confi g.
-
ALE02
Maximum operating pressure on Driver 2
Automatic
Confi g.
Confi g.
-
ALE03
EEV motor error on Driver 2
Automatic
Confi g.
Confi g.
-
ALE03
High condensing temperature on Driver 2
Automatic
Confi g.
Confi g.
-
ALE03
Low suction temperature on Driver 2
Automatic
Confi g.
Confi g.
-
ALE04
Low superheat on Driver 2
Automatic
Confi g.
Confi g.
-
ALE04
Low operating pressure on Driver 2
Automatic
Confi g.
Confi g.
-
ALE04
Maximum operating pressure on Driver 2
Automatic
Confi g.
Confi g.
-
ALE05
EEPROM error on Driver 1 in PLB1
Automatic
Confi g.
Confi g.
-
ALE05
Probe S1 error on Driver 1 in PLB1
Automatic
Confi g.
Confi g.
-
ALE05
Probe S2 error on Driver 1 in PLB1
Automatic
Confi g.
Confi g.
-
ALE05
Probe S3 error on Driver 1 in PLB1
Automatic
Confi g.
Confi g.
-
ALE05
Probe S4 error on Driver 1 in PLB1
Automatic
Confi g.
Confi g.
-
ALE05
Offl
ine error on Driver 1 in PLB1
Automatic
Confi g.
Confi g.
-
ALE05
Battery error on Driver 1 in PLB1
Automatic
Confi g.
Confi g.
-
ALE07
EEPROM error on Driver 1 in PLB3
Automatic
Confi g.
Confi g.
-
ALE07
Probe S1 error on Driver 1 in PLB3
Automatic
Confi g.
Confi g.
-
ALE07
Probe S2 error on Driver 1 in PLB3
Automatic
Confi g.
Confi g.
-
ALE07
Probe S3 error on Driver 1 in PLB3
Automatic
Confi g.
Confi g.
-
ALE07
Probe S4 error on Driver 1 in PLB3
Automatic
Confi g.
Confi g.
-
ALE07
Offl
ine error on Driver 1 in PLB3
Automatic
Confi g.
Confi g.
-
ALE07
Battery error on Driver 1 in PLB3
Automatic
Confi g.
Confi g.
-
ALE08
EEPROM error on Driver 2 in PLB1
Automatic
Confi g.
Confi g.
-
ALE08
Probe S1 error on Driver 2 in PLB1
Automatic
Confi g.
Confi g.
-
ALE08
Probe S2 error on Driver 2 in PLB1
Automatic
Confi g.
Confi g.
-
ALE08
Probe S3 error on Driver 2 in PLB1
Automatic
Confi g.
Confi g.
-
ALE08
Probe S4 error on Driver 2 in PLB1
Automatic
Confi g.
Confi g.
-
ALE08
Offl
ine error on Driver 2 in PLB1
Automatic
Confi g.
Confi g.
-
ALE08
Battery error on Driver 2 in PLB1
Automatic
Confi g.
Confi g.
-
ALE10
EEPROM error on Driver 2 in PLB3
Automatic
Confi g.
Confi g.
-
ALE10
Probe S1 error on Driver 2 in PLB3
Automatic
Confi g.
Confi g.
-
ALE10
Probe S2 error on Driver 2 in PLB3
Automatic
Confi g.
Confi g.
-
ALE10
Probe S3 error on Driver 2 in PLB3
Automatic
Confi g.
Confi g.
-
ALE10
Probe S4 error on Driver 2 in PLB3
Automatic
Confi g.
Confi g.
-
ALE10
Offl
ine error on Driver 2 in PLB3
Automatic
Confi g.
Confi g.
-
ALE10
Battery error on Driver 2 in PLB3
Automatic
Confi g.
Confi g.
-
ALE11
Parameter transmission error on Driver 1
Automatic
0
Confi g.
-
ALE12
Parameter transmission error on Driver 2
Automatic
0
Confi g.
-
ALE13
FW compatibility error on Driver 1
Automatic
0
Confi g.
-
ALE14
FW compatibility error on Driver 2
Automatic
0
Confi g.
-
Tab. A.e