pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Eid06
Prop Gain:
Control proportional gain (valve 1)
15.0
0.0…800.0
Integral time:
Control integral time (valve 1)
150
s
0…1000
Derivat.time:
Control derivative time (valve 1)
5.0
s
0…1000
Eid08
LowSH protect.:
Integral time with low superheat protection (valve 1)
10.0
s
0.0…800.0
LOP protection:
Integral time with low operating pressure protection (valve 1)
10.0
s
0.0…800.0
MOP protection:
Integral time with maximum operating pressure protection (valve 1)
20.0
s
0.0…800.0
Eid10
Threshold:
High condensing temperature protection activation threshold (valve 1) 30.0
°C/°F
-60.0…200.0
Integr.time:
Integral time with high condensing temperature protection (valve 1)
0.5
s
0.0…800.0
Alarm timeout
High condensing temperature alarm delay (valve 1)
600
s
0…18000
Eid11
LowSH:
Low superheat alarm delay (valve 1)
300
s
0…18000
LOP:
Low operating pressure alarm delay (valve 1)
300
s
0…18000
MOP:
Maximum operating pressure alarm delay (valve 1)
600
s
0…18000
Eid13
Threshold
Low suction temperature protection threshold (valve 1)
-50.0
°C/°F
-60.0…200.0
Timeout
Low suction temperature alarm delay (valve 1)
300
s
0…18000
Eid15
Valve A opening at
start-up
Valve opening at start of control (valve 2)
50
%
0…100
Eid17
Valve A opened in
stand-by
Enable valve opening with control not active (valve 2)
NO
NO/YES
Start-up delay after
defrost
Start control delay after defrost (valve 2)
10
min
0…60
Valve A preposit. delay
Stationary time when valve pre-positions (valve 2)
6
s
0…18000
Eid19
Prop Gain:
Control proportional gain (valve 2)
15.0
0.0…800.0
Integral time:
Control integral time (valve 2)
150
s
0…1000
Derivat.time:
Control derivative time (valve 2)
5.0
s
0…1000
Eid21
LowSH protect.:
Integral time with low superheat protection (valve 2)
10.0
s
0.0…800.0
LOP protection:
Integral time with low operating pressure protection (valve 2)
10.0
s
0.0…800.0
MOP protection:
Integral time with maximum operating pressure protection (valve 2)
20.0
s
0.0…800.0
Eid23
Threshold:
High condensing temperature protection activation threshold (valve 2) 30.0
°C/°F
-60.0…200.0
Integr.time:
Integral time with high condensing temperature protection (valve 2)
0.5
s
0.0…800.0
Alarm timeout
High condensing temperature alarm delay (valve 2)
600
s
0…18000
Eid24
LowSH:
Low superheat alarm delay (valve 2)
300
s
0…18000
LOP:
Low operating pressure alarm delay (valve 2)
300
s
0…18000
MOP:
Maximum operating pressure alarm delay (valve 2)
600
s
0…18000
Eid26
Threshold
Low suction temperature protection threshold (valve 2)
-50.0
°C/°F
-60.0…200.0
Timeout
Low suction temperature alarm delay (valve 2)
300
s
0…18000
Eie02
Min.steps
Minimum step confi guration, valve 1
50
0…9999
Max.steps
Maximum step confi guration, valve 1
480
0…9999
Closing steps
Closing step confi guration, valve 1
500
0…9999
Eie04
Min.steps
Minimum step confi guration, valve 2
50
0…9999
Max.steps
Maximum step confi guration, valve 2
480
0…9999
Closing steps
Closing step confi guration, valve 2
500
0…9999
Eif01
Enable EVD in PLB x
Enable the EVD management on current board
NO
NO/YES
EVD valves number
Number of drivers managed
1
1 / 2
EVS 1 Address
Serial address of driver 1
198
0…207
EVS 2 Address
Serial address of driver 2
199
0…207
Eif02
Defaults:
Run driver parameter setting procedure
NO
Force Parameters:
Override driver parameter settings
NO
Regulation based on:
Select cooling capacity used for control
LINE 1 COMP
LINE 1 COMP. / LINE 2 COMP
Eif03
Valve:
Type of valve connected to the driver
CAREL EXV
USER DEFINED / CAREL EXV
/ ALCO EX4 / ALCO EX5 /
ALCO EX6 / ALCO EX7 /
ALCO EX8 CAREL RECOM-
MENDED / ALCO EX8 ALCO
SPECIFICATION / SPORLAN SEI
0.5-11 / SPORLAN SER 1.5-20
/ SPORLAN SEI 30 / SPORLAN
SEI 50 / SPORLAN SEH 100 /
SPORLAN SEH 175 / Danfoss
ETS 12.5-25B / Danfoss ETS 50B
/ Danfoss ETS 100B / Danfoss
ETS 250 / Danfoss ETS 400 /
TWO CAREL EXV TOGETHER /
SPORLAN SER(I) G, J, K / Dan-
foss CCM 10-20-30 / Danfoss
CCM 40
Eif05
Main Regulation:
Main control for the valve, for details refer to 0300005EN
R404 CON-
DENSER FOR
SUBCRITICAL
CO2
Possible control functions in
0300005EN
Auxiliary regulation:
Safety or auxiliary control
INVERSE HIGH
CONDENS.
TEMP.
PROTECTION
ON S3
Possible control functions in
0300005EN
Eif06
Auxiliary refrigerant:
Refrigerant used for P -> T conversion of probe S3 with high condensing
temperature protection
R744
Eif09
S1 probe alarm manag:
Type of action in the event of probe S1 fault
VALVE AT
FIXED POS.
NO ACTION / VALVE FORCE
CLOSED / VALVE AT FIXED POS
/ USE BACKUP S3
S2 probe alarm manag:
Type of action in the event of probe S2 fault
VALVE AT
FIXED POS.
NO ACTION / VALVE FORCE
CLOSED / VALVE AT FIXED POS
/ USE BACKUP S4
Eif11
DC power supply
Confi gure the type of power supply used for the driver
NO
NO / YES