95
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Code
Description
Reset
Delay
Alarm relay
Action
ALC30
Alarm 2, compressor 5
Manual/automatic
Settable
Settable
Shutdown compressor 5
ALC31
Alarm 3, compressor 5
Manual/automatic
Settable
Settable
Shutdown compressor 5
ALC32
Alarm 4, compressor 5
Manual/automatic
Settable
Settable
Shutdown compressor 5
ALC33
Alarm 6, compressor 5
Manual/automatic
Settable
Settable
Shutdown compressor 5
ALC34
Alarm 7, compressor 5
Manual/automatic
Settable
Settable
Shutdown compressor 5
ALC35
Alarm 7, compressor 5
Manual/automatic
Settable
Settable
Shutdown compressor 5
ALC36
Alarm 1, compressor 6
Manual/automatic
Settable
Settable
Shutdown compressor 6
ALC37
Alarm 2, compressor 6
Manual/automatic
Settable
Settable
Shutdown compressor 6
ALC38
Alarm 3, compressor 6
Manual/automatic
Settable
Settable
Shutdown compressor 6
ALC39
Alarm 4, compressor 6
Manual/automatic
Settable
Settable
Shutdown compressor 6
ALC40
Alarm 5, compressor 6
Manual/automatic
Settable
Settable
Shutdown compressor 6
ALC41
Alarm 6, compressor 6
Manual/automatic
Settable
Settable
Shutdown compressor 6
ALC42
Alarm 7, compressor 6
Manual/automatic
Settable
Settable
Shutdown compressor 6
ALC43
Alarm 1, compressor 7
Manual/automatic
Settable
Settable
Shutdown compressor 7
ALC44
Alarm 2, compressor 7
Manual/automatic
Settable
Settable
Shutdown compressor 7
ALC45
Alarm 1, compressor 8
Manual/automatic
Settable
Settable
Shutdown compressor 8
ALC46
Alarm 2, compressor 8
Manual/automatic
Settable
Settable
Shutdown compressor 8
ALC47
Alarm 1, compressor 9
Manual/automatic
Settable
Settable
Shutdown compressor 9
ALC48
Alarm 2, compressor 9
Manual/automatic
Settable
Settable
Shutdown compressor 9
ALC49
Alarm 1, compressor 10
Manual/automatic
Settable
Settable
Shutdown compressor 10
ALC50
Alarm 1, compressor 11
Manual/automatic
Settable
Settable
Shutdown compressor 11
ALC51
Alarm 1, compressor 12
Manual/automatic
Settable
Settable
Shutdown compressor 12
ALC52
Alarm 1, compressor 1, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 1, line 2
ALC53
Alarm 2, compressor 1, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 1, line 2
ALC54
Alarm 3, compressor 1, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 1, line 2
ALC55
Alarm 4, compressor 1, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 1, line 2
ALC56
Alarm 5, compressor 1, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 1, line 2
ALC57
Alarm 6, compressor 1, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 1, line 2
ALC58
Alarm 7, compressor 1, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 1, line 2
ALC59
Alarm 1, compressor 2, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 2, line 2
ALC60
Alarm 2, compressor 2, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 2, line 2
ALC61
Alarm 3, compressor 2, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 2, line 2
ALC62
Alarm 4, compressor 2, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 2, line 2
ALC63
Alarm 5, compressor 2, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 2, line 2
ALC64
Alarm 6, compressor 2, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 2, line 2
ALC65
Alarm 7, compressor 2, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 2, line 2
ALC66
Alarm 1, compressor 3, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 3, line 2
ALC67
Alarm 2, compressor 3, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 3, line 2
ALC68
Alarm 3, compressor 3, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 3, line 2
ALC69
Alarm 4, compressor 3, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 3, line 2
ALC70
Alarm 5, compressor 3, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 3, line 2
ALC71
Alarm 6, compressor 3, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 3, line 2
ALC72
Alarm 7, compressor 3, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 3, line 2
ALC73
Alarm 1, compressor 4, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 4, line 2
ALC74
Alarm 2, compressor 4, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 4, line 2
ALC75
Alarm 3, compressor 4, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 4, line 2
ALC76
Alarm 4, compressor 4, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 4, line 2
ALC77
Alarm 5, compressor 4, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 4, line 2
ALC78
Alarm 6, compressor 4, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 4, line 2
ALC79
Alarm 7, compressor 4, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 4, line 2
ALC80
Alarm 1, compressor 5, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 5, line 2
ALC81
Alarm 2, compressor 5, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 5, line 2
ALC82
Alarm 3, compressor 5, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 5, line 2
ALC83
Alarm 4, compressor 5, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 5, line 2
ALC84
Alarm 5, compressor 5, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 5, line 2
ALC85
Alarm 6, compressor 5, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 5, line 2
ALC86
Alarm 7, compressor 5, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 5, line 2
ALC87
Alarm 1, compressor 6, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 6, line 2
ALC88
Alarm 2, compressor 6, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 6, line 2
ALC89
Alarm 3, compressor 6, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 6, line 2
ALC90
Alarm 4, compressor 6, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 6, line 2
ALC91
Alarm 5, compressor 6, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 6, line 2
ALC92
Alarm 6, compressor 6, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 6, line 2
ALC93
Alarm 7, compressor 6, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 6, line 2
ALC94
Alarm 1, compressor 7, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 7, line 2
ALC95
Alarm 2, compressor 7, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 7, line 2
ALC96
Alarm 1, compressor 8, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 8, line 2
ALC97
Alarm 2, compressor 8, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 8, line 2
ALC98
Alarm 1, compressor 9, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 9, line 2
ALC99
Alarm 2, compressor 9, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 9, line 2
ALCaa
Alarm 1, compressor 10, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 10, line 2
ALCab
Alarm 1, compressor 11, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 11, line 2
ALCac
Alarm 1, compressor 12, line 2
Manual/automatic
Settable
Settable
Shutdown compressor 12, line 2
ALCad
High oil sump temperature, Digital Scroll™
Manual/automatic
Settable
R2
Shutdown compressor
ALCae
High discharge temperature, Digital Scroll™
Manual/automatic
Settable
R2
Shutdown compressor
ALCaf
High oil dilution, Digital Scroll™
Manual/automatic
Settable
R2
Shutdown compressor
ALCag
High oil sump temperature, Digital Scroll™, line 2
Manual/automatic
Settable
R2
Shutdown compressor
ALCah
High discharge temperature, Digital Scroll™, line 2
Manual/automatic
Settable
R2
Shutdown compressor
ALCai
High oil dilution, Digital Scroll™, line 2
Manual/automatic
Settable
R2
Shutdown compressor
ALCal
High discharge temperature compressors 1 to 6
Automatic
60s
R2
Related functions disabled
ALCam
High discharge temperature compressors 1 to 6, line 2
Automatic
60s
R2
Related functions disabled
AlCan
Compressor envelope
Manual
Settable
R1
Shutdown compressor
ALCao
High compressor oil temperature, line 1
Automatic
Settable
R2
-
AlCap
High compressor oil temperature, line 2
Automatic
Settable
R2
-
ALF01
Fan circuit breaker
Manual/automatic
Settable
R2
Shutdown fans
ALF02
Fan circuit breaker, line 2
Manual/automatic
Settable
R2
Shutdown fans
ALG01
Clock error
Automatic
-
R2
Related functions disabled
ALG02
Extended memory error
Automatic
-
R2
Related functions disabled
ALG11
Generic high temperature alarms 1 to 5, PLB1
Manual/automatic
Settable
Settable
-
ALG12
Generic high temperature alarms 1 to 5, PLB2
Manual/automatic
Settable
Settable
-
ALG13
Generic high temperature alarms 1 to 5, PLB3
Manual/automatic
Settable
Settable
-
ALG14
Generic high temperature alarms 1 to 5, PLB4
Manual/automatic
Settable
Settable
-