57
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display Description
Description
Default
UOM
Values
Bba54
Heat reclaim pump
force
Manual operating status for heat recovery pump (line 1)
OFF
---
OFF / ON
Bba55
ChillBooster
force
Manual operating status for ChillBooster (line 1)
OFF
---
OFF / ON
Bba57
Fan1
force
Manual operating status for fan 1 (line 2)
OFF
---
OFF / ON
…
…
…
…
…
Bba72
Fan16
force
Manual operating status for fan 16 (line 2)
OFF
---
OFF / ON
Bba73
Heat reclaim pump
force
Manual operating status for heat recovery pump (line 2)
OFF
---
OFF / ON
Bba74
ChillBooster
force
Manual operating status for ChillBooster (line 2)
OFF
---
OFF / ON
Bbb05
Compressor 1
Force to
Manual continuous capacity request for compressor 1 (line 1)
0.0
%
0.0…100.0
Bbb06
Oil cool pump
Force to
Manual request for oil cooling pump (line 1)
0.0
%
0.0…100.0
Bbb07
Compressor 1
Force to
Manual continuous capacity request for compressor 1 (line 2)
0.0
%
0.0…100.0
Bbb08
Oil cool pump
Force to
Manual request for oil cooling pump (line 2)
0.0
%
0.0…100.0
Bbb09
Fan1
Force to
Manual continuous capacity request for fan 1 (line 1)
0.0
%
0.0…100.0
Bbb10
Heat reclaim pump
force
Manual request for heat recovery pump (line 1)
0.0
%
0.0…100.0
Bbb11
Fan1
Force to
Manual continuous capacity request for fan 1 (line 2)
0.0
%
0.0…100.0
Bbb12
Heat reclaim pump
force
Manual request for heat recovery pump (line 2)
0.0
%
v
Bc01
Test Dout
Enable DO test mode
NO
---
NO / YES
Timeout
Test mode duration after last button pressed
10
min
0…500
Bc02
Test Aout
Enable AO test mode
NO
---
NO / YES
Timeout
Test mode duration after last button pressed
10
min
0…500
Bca10
DO1
DO 1 logic for test
NO
---
NO / NC
DO 1 value for test
OFF
---
OFF / ON
…
…
…
…
…
…
Bca26
DO29
DO 29 logic for test
NO
---
NO / NC
DO 29 value for test
OFF
---
OFF / ON
Bcb10
AO1
AO 1 value for test
0.0
---
0.0…100.0
…
…
…
…
…
Bcb12
AO6
AO 6 value for test
0.0
---
0.0…100.0
Mask index
Display description
Description
Default
UOM
Values
C.Compressors
(*) (The I/Os available depend on the selected confi guration, the following are just some examples. For the complete list of I/O positions available see
Appendix A.5)
Caa01
DI
Alarm 1 for compressor 1 DI position (line 1)
03
---
---, 01…18, B1…B10 (****)
Status (display only)
Status of alarm 1 for compressor 1 DI (line 1)
---
---
Closed / Open
Logic
Logic of alarm 1 for compressor 1 DI (line 1)
NC
---
NC / NO
Function (display only)
Alarm 1 for compressor 1 function status (line 1)
---
---
Not active / Active
…
…
…
…
…
…
Caa08
Line relay DO
Compressor 1 part winding or star DO position and status (On/Off )
display (line 1)
…
---
---, 01…29 (****)
Part winding DO/Star
relay DO (*)
Compressor 1 delta DO position and status (On/Off ) display (line 1)
…
---
---, 01…29 (****)
---/ Delta relay DO (*)
Compressor 1 line DO position and status (On/Off ) display (line 1)
…
---
---, 01…29 (****)
Logic
DO logic to start compressor 1 (line 1)
NC
---
NC / NO
Caa09
DO
Unloader 1 for compressor 1 DO position (line 1)
…
---
---, 01…29 (****)
Status (display only)
Status of unloader 1 for compressor 1 DI (line 1)
---
---
Closed / Open
Logic
Logic of unloader 1 for compressor 1 DI (line 1)
NC
---
NC / NO
Function (display only)
Unloader 1 for compressor 1 function status (line 1)
---
---
Not active / Active
…
…
…
…
…
…
Caa14
AO
Compressor modulating device AO position (line 1)
0
---
---, 01…06 (****)
Type (****)
Type of output, PWM / phase control for compressor modulating device
(line 1)
FCS1*-CON-
VONOFF
---
----
FCS1*-CONVONOFF
FCS3*-CONV010"
Status (display only)
Modulating device output value (line 1)
0
%
0.0…100.0
…
…
…
…
…
…
Caaal
---
Suction pressure probe position (line1)
B1
---
---, B1…B10 (****)
---
Suct pressure probe type (line 1)
4-20mA
---
----
0-1V
0-10V
4-20mA
0-5V
--- (display only)
Suction temperature value (line 1)
---
…
… (**)
Upper value
Suct pressure maximum limit (line 1)
7,0 barg
…
… (**)
Lower value
Suct pressure minimum limit (line 1)
-0,5 barg
…
… (**)
Calibration
Suction pressure probe adjustment (line 1)
0.0 barg
…
… (**)
…
…
…
…
…
…
Cab01
Regulation by
Compressor control by temperature or pressure (line 1)
PRESSURE
---
PRESSURE TEMPERATURE
Regulation type
Compressor control type (line 1)
NEUTRAL
ZONE
---
PROPORTIONAL BAND
NEUTRAL ZONE
Cab02
Minimum
Compressor setpoint lower limit (line 1)
… (**)
…
… (**)
Maximum
Compressor setpoint higher limit (line 1)
… (**)
…
… (**)
Cab03
Setpoint
Compressor setpoint (line 1)
… (**)
…
… (**)