pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Eif12
Valve:
Type of valve connected to the driver
CAREL EXV
USER DEFINED / CAREL EXV /
ALCO EX4 / ALCO EX5 / ALCO
EX6 / ALCO EX7 / ALCO EX8
CAREL RECOMMENDED / ALCO
EX8 ALCO SPECIFICATION /
SPORLAN SEI 0.5-11 / SPORLAN
SER 1.5-20 / SPORLAN SEI 30
/ SPORLAN SEI 50 / SPORLAN
SEH 100 / SPORLAN SEH 175 /
Danfoss ETS 12.5-25B / Danfoss
ETS 50B / Danfoss ETS 100B
/ Danfoss ETS 250 / Danfoss
ETS 400 / TWO CAREL EXV
TOGETHER / SPORLAN SER(I) G,
J, K / Danfoss CCM 10-20-30 /
Danfoss CCM 40
Eif14
Main Regulation:
Main control for the valve, for details refer to 0300005EN
R404 CON-
DENSER FOR
SUBCRITICAL
CO2
Possible control functions in
0300005EN
Auxiliary regulation:
Safety or auxiliary control
INVERSE HIGH
CONDENS.
TEMP.
PROTECTION
ON S3
Possible control functions in
0300005EN
Eif15
Auxiliary refrigerant:
Refrigerant used for P -> T conversion of probe S3 with high condensing
temperature protection
R744
Eif18
S1 probe alarm manag:
Type of action in the event of probe S1 fault
VALVE AT
FIXED POS.
NO ACTION / VALVE FORCE
CLOSED / VALVE AT FIXED POS
/ USE BACKUP S3
S2 probe alarm manag:
Type of action in the event of probe S2 fault
VALVE AT
FIXED POS.
NO ACTION / VALVE FORCE
CLOSED / VALVE AT FIXED POS
/ USE BACKUP S4
Eif20
DC power supply
Confi gure the type of power supply used for the driver
NO
NO / YES
The following parameters refer to line 2, for details see the corresponding parameters for line 1 above
Eaba04
---
Oil temperature probe position (line 2)
B1
---
---, B1…B10 (****)
---
Oil temperature probe type (line 2)
4-20mA
---
---
NTC - PT1000 - 0-1V - 0-10V -
4-20mA - 0-5V - HTNTC
--- (display only)
Oil temperature probe value (line 2)
---
…
… (**)
Upper value
Oil temperature probe max. limit (line 2)
30.0 barg
…
… (**)
Lower value
Oil temperature probe min. limit (line 2)
0.0 barg
…
… (**)
Calibration
Oil temperature probe adjustment (line 2)
0.0 barg
…
… (**)
…
…
…
…
…
…
Eabb04
Oil pumps number
Number of oil pumps for common oil cooler (line 2)
0
---
0 to 1 (digital input)
0 to 2 (Digital outputs)
Enable Aout pump
Enable AO of common oil cooler pump (line 2)
YES
---
NO (Digital outputs)
YES (digital input)
…
…
…
…
…
…
Ebba01
DO
Subcooling valve DO position (line 2)
…
---
---, 01…29 (****)
Status (display only)
Status of subcooling valve DO (line 2)
---
---
Closed / Open
Logic
Logic of subcooling valve (line 2)
NO
---
NC / NO
Function (display only)
Subcooling valve function status (line 2)
---
---
Not active / Active
…
…
…
…
…
…
Ebbb01
Subcooling control
Enable subcooling function (line2)
NO
---
NO / YES
---
Subcooling control type (line 2)
COND&
LIQUID TEMP.
---
COND&LIQUID TEMP.
LIQUID TEMP. ONLY
Threshold
Threshold for subcooling control (line 2)
0.0 °C
…
-9999.9…9999.9
Subcool.value
(display only)
Value of subcooling (line 2)
0.0 °C
…
-999.9…999.9
…
…
…
…
…
…
Ecbb04
Economizer
Enable economizer function (line 2)
NO
---
NO / YES
Compr.Power Thr.
Capacity percent threshold for economizer activation (line 2)
0
%
0…100
Press.Lim.
Condensing temperature threshold for economizer activation (line 2)
0.0 °C
…
-999.9…999.9
Disch.T.Thr.
Discharge temperature threshold for economizer activation (line 2)
0.0 °C
…
-999.9…999.9
…
…
…
…
…
…
Edba01
---
Compressor 1 discharge temperature probe position (line 2)
B1
---
---, B1…B10 (****)
---
Compressor 1 discharge temperature probe type (line 2)
4-20mA
---
---
NTC - PT1000 - 0-1V - 0-10V -
4-20mA - 0-5V - HTNTC
--- (display only)
Compressor 1 discharge temperature probe value (line 2)
---
…
… (**)
Edba01
Upper value
Compressor 1 discharge temperature probe max. limit (line 2)
30.0 barg
…
… (**)
Lower value
Compressor 1 discharge temperature probe min. limit (line 2)
0.0 barg
…
… (**)
Calibration
Compressor 1 discharge temperature probe adjustment (line 2)
0.0 barg
…
… (**)
…
…
…
…
…
…
Edbb01
Liquid Injection
Enable liquid injection function (line 2)
DIS
---
DIS / EN
Threshold
Liquid injection setpoint (line 2)
70.0 °C
…
… (**)
Diff erential
Liquid injection diff erential (line 2)
5,0
…
… (**)
…
…
…
…
…
…
Eeba02
DI
Heat recovery from digital input DI position (line 2)
…
---
---, 01…18, B1…B10 (****)
Status
Status of heat recovery DI (line 2)
---
---
Closed / Open
Logic
Logic of heat recovery DI (line 2)
NC
---
NC / NO
Function
Status of heat recovery from digital input DI function (line 2)
---
---
Not active / Active
Eebb01
Enable Heat Reclaim
Enable heat recovery function (line 2)
NO
---
NO / YES
…
…
…
…
…
…
Egba01
DI
ChillBooster fault DI position (line 2)
---
---
---, 01…18, B1…B10 (****)
Status
Status of ChillBooster fault DI (line 2)
---
---
Closed / Open
Logic
Logic of ChillBooster fault DI (line 2)
NC
---
NC / NO
Function
Status of ChillBooster fault DI (line 21)
---
---
Not active / Active