pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Cab04/Cab6 (**)
Reg.type
Type for proportional control (line 1)
PROPORT.
---
PROPORTIONAL PROP.+INT.
Integral time
Integral time for proportional control (line 1)
300
s
0…999
Cab05/Cab7 (**) Diff erential
Diff erential for proportional control (line 1)
… (**)
…
… (**)
Cab08/Cab10 (**)
NZ diff .
Neutral zone control diff erential (line 1)
… (**)
…
… (**)
Activ.diff .
Neutral zone control diff erential for device activation (line 1)
… (**)
…
… (**)
Deact.diff .
Neutral zone control diff erential for device deactivation (line 1)
… (**)
…
… (**)
Cab09/Cab11 (**)
En.force off power
Enable capacity immediate decreasing to 0 (line 1)
NO
---
NO / YES
Setp.for force off
Threshold for capacity decreasing to 0 (line 1)
… (**)
…
… (**)
Cab12
Power load to 100% min
time
Minimum time to increase capacity request to 100%, Neutral zone
control (suction line 1)
15
s
0…9999
Power load to 100% max
time
Maximum time to increase capacity request to 100%, Neutral zone
control (suction line 1)
90
s
0…9999
Cab13
Power unload to 0% min
time
Minimum time to decrease capacity request to 0%, Neutral zone control
(suction line 1)
30
s
0…9999
Power unload to 0% max
time
Maximum time to decrease capacity request to 0%, Neutral zone control
(suction line 1)
180
s
0…9999
Cab20
Enable Aux cont.
Enable auxiliary control
NO
NO/YES
Probe type
Probe used for auxiliary control
PRESSURE
PRESSURE/TEMPERATURE
Refrig. type
Type of refrigerant in auxiliary circuit
R404A
R22 - R134a - R404A - R407C
-R410A - R507A - R290 - R600
- R600a - R717 -R744 - R728 -
R1270 - R417A - R422D -R413A -
R422A - R423A - R407A - R427A
- R245Fa - R407F - R32\
Cac01
Working hours
Compressor 1
Compressor 1 operating hours (line 1)
---
h
0…999999
(Check in…)
Compressor 1 remaining operating hours (line 1)
…
h
0…999999
Compressor 2
Compressor 2 operating hours (line 1)
---
h
0…999999
(Check in…)
Compressor 2 remaining operating hours (line 1)
…
h
0…999999
…
…
…
…
…
…
Cac11
Working hours
Compressor 11
Compressor 11 operating hours (line 1)
---
h
0…999999
(Check in…)
Compressor 11 remaining operating hours (line 1)
…
h
0…999999
Compressor 12
Compressor 12 operating hours (line 1)
---
h
0…999999
(Check in…)
Compressor 12 remaining operating hours (line 1)
…
h
0…999999
Cac13
Compressor threshold
working hours
Compressor maintenance threshold hours (line 1)
88000
h
0…9999999
Cac14
Compressor hours reset
Reset compressor operating hours (line 1)
N
---
NO / YES
Cad01
Enable suction setpoint
compensation
Enable setpoint compensation (suction line 1)
NO
---
NO / YES
Enable compensation by
analog IN
Enable setpoint compensation by probe (suction line 1)
NO
---
NO / YES
Cad02
Winter off set
Off set applied for Winter period
0.0
…
-999.9…999.9
Closing off set
Off set applied for closing period
0.0
…
-999.9…999.9
Cad03
Enable setpoint compen-
sation by scheduler
Enable scheduler setpoint compensation (suction line 1)
NO
---
NO / YES
Cad04
Activ.Time Bands
Day of the week
---
---
MON, TUE, ...SUN
TB1: --:-- -> --:--
Time band 1 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
…
…
…
…
…
…
…
TB4: --:-- -> --:--
Time band 4 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
…
…
Changes
Time band change action
---
---
---
CONFIRM&SAVE
LOAD PREVIOUS
CLEAR ALL
Copy to
Copy settings to other days
0
---
MONDAY…SUNDAY;
MON-FRI; MON-SAT;
SAT&SUN; ALL DAYS
Cad05
Change set by DI
Enable setpoint compensation by digital input (suct/cond line 1)
NO
---
NO / YES
Cad06
---
Position of the probe for suction pressure setpoint compensation (line1) ---
---
---, B1…B10 (****)
---
Type of the probe for suction pressure setpoint compensation (line1)
4-20mA
---
----
0-1V - 0-10V- 4-20mA- 0-5V
--- (display only)
Compensation value (line 1)
---
…
-99.9…99.9
max
Maximum value of compensation (line 1)
---
…
-99.9…99.9
min
Minimum value of compensation (line 1)
---
…
-99.9…99.9
Cad08
Enable fl oating suction
setpoint
Enable fl oating setpoint (suction line 1)
NO
---
NO / YES
Cad09
Maximum fl oating
setpoint
Max compressor fl oating setpoint settable (line 1)
… (**)
…
… (**)
Minimum fl oating
setpoint
Minimum compressor fl oating setpoint settable (line 1)
… (**)
…
… (**)
Cad10
Max.setpoint variation
admitted
Maximum delta admitted for fl oating setpoint (suction line 1)
… (**)
…
… (**)
Offl
ine decreasing time
Reduction time when supervisor is offl
ine for fl oating setpoint
(suction line 1)
0
min
0…999
Cad11
Enable interactions with
pLoads
Enable interactions with pLoads (line 1)
NO
---
NO / YES
Pressure threshold
disabled
Suction pressure threshold for disabling pLoads (line 1)
…(**)
…
0.0 to 99.9
Reactivate delay
pLoads activation delay, previously disabled by a threshold
60
s
60…9999