64
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Dbb01
Regulation by
Condenser control by temperature or pressure (line 2)
PRESSURE
---
PRESSURE TEMPERATURE
Regulation type
Condenser control type (line 2)
NEUTRAL
ZONE
---
PROPORTIONAL BAND
NEUTRAL ZONE
…
…
…
…
…
…
Dbd01
Enable condensing
setpoint compensation
Enable setpoint compensation (condenser line 2)
NO
---
NO
YES
…
…
…
…
…
…
Dbe01
Cond.temperature/pres-
sure high alarm
Type of high condensing pressure/temperature alarm threshold
(line 2)
ABSOLUTE
---
ABSOLUTE
RELATIVE
Threshold
High condensing pressure/temperature alarm threshold (line 2)
24,0 barg
…
… (**)
…
…
…
…
…
…
Dbf01
Number of present fans
Number of fans (line 2)
3
---
0 to 16
…
…
…
…
…
…
Dbg01
Modulate speed device
Fan driver type (line 2)
NONE
---
NONE
INVETER
PHASE CONTROL
Type (****)
Type of output, PWM / phase control for condenser modulating device
(line 2)
----
---
----
MCHRTF*
FCS3*-CONV010
…
…
…
…
…
…
Mask index
Display description
Description
Default
UOM
Values
E.Other funct.
(The I/Os available depend on the selected confi guration, the following are just some examples. For the complete list of I/O positions available
see Appendix A.5)
Eaaa04
---
Oil temperature probe position (line1)
B1
---
---, B1…B10 (****)
---
Oil temperature probe type (line 1)
4-20mA
---
---
NTC - PT1000 - 0-1V - 0-10V -
4-20mA - 0-5V - HTNTC
--- (display only)
Oil temperature probe value (line 1)
---
…
… (**)
Upper value
Oil temperature probe max. limit (line 1)
30.0 barg
…
… (**)
Lower value
Oil temperature probe min. limit (line 1)
0.0 barg
…
… (**)
Calibration
Oil temperature probe adjustment (line 1)
0.0 barg
…
… (**)
…
…
…
…
…
…
Eaaa45
DO
Oil level valve DO position, compressor 6 (line 1)
03
---
---, 01…29 (****)
Status (display only)
Oil level valve DO status, compressor 6 (line 1)
---
---
Closed / Open
Logic
Oil level valve DO logic, compressor 6 (line 1)
NC
---
NC / NO
Function (display only)
Oil level function status, compressor 6 (line 1)
---
---
Not active / Active
Eaab04
Common oil cooler
Enable common oil cooling (line 1)
YES
---
NO / YES
Oil pumps number
Number of oil pumps for common oil cooler (line 1)
0
---
0 to 1 (Analog output)
0 to 2 (Digital outputs)
Enable Aout pump
Enable AO of common oil cooler pump (line 1)
YES
---
NO (Digital outputs)
YES (Analog output)
Eaab05
Setpoint
Common oil cooler setpoint (line 1)
0.0 °C
…
… (**)
Diff erential
Common oil cooler diff erential (line 1)
0.0 °C
…
-9.9…9.9
Eaab06
Pump start delay
Time delay before the start-up of pump 2 after pump1 turns on (line 1)
0
s
0…999
Eaab07
Oil pumps number
Screw compressors: number of oil cooler pumps enabled (line1)
0
---
0 to 1 (Analog output)
0 to 2 (Digital outputs)
Enable Aout pump
Screw compressors: enable AO for oil cooler pump (line 1)
YES
---
NO (Digital outputs)
YES (Analog output)
Eaab08
Setpoint
Screw compressors: oil temperature setpoint (line 1)
0.0
°C/°F
…
Diff erential
Screw compressors: oil temperature diff erential (line 1)
0.0
°C/°F
…
Eaab09
Threshold
Common oil high temperature alarm threshold (line 1)
100.0 °C
°C/°F
…
Diff erential
Common oil high temperature alarm diff erential (line 1)
10.0 °C
°C/°F
…
Delay
Common oil high temperature alarm delay (line 1)
0
s
0 to 32767
Eaab10
En.oil lev.manag.
Enable oil level management (line 1)
NO
---
NO / YES
Num.Alarm oil level
Number of compressor alarm associated with oil level (line 1)
0
---
0 to 4/7 (*)
Eaab11
Time open
Oil level valve opening time (line 1)
0
s
0…999
Time close
Oil level valve closing time (line 1)
0
s
0…999
Ebaa01
DO
Subcooling valve DO position (line 1)
…
---
---, 01…29 (****)
Status (display only)
Status of subcooling valve DO (line 1)
---
---
Closed / Open
Logic
Logic of subcooling valve (line 1)
NO
---
NC / NO
Function (display only)
Subcooling valve function status (line 1)
---
---
Not active / Active
Ebab01
Subcooling control
Enable subcooling function (line 1)
NO
---
NO / YES
---
Subcooling control type (line 1)
BY COND. &
LIQUID TEMP.
---
BY COND.& LIQUID TEMP.
ONLY BY LIQUID. TEMP.
Threshold
Threshold for subcooling control (line 1)
0.0 °C
…
-9999.9…9999.9
Subcool.value
(display only)
Subcooling value (line 1)
0.0 °C
…
-999.9…999.9
Ecaa01
---
Discharge temperature probe position, compressor 1 (line 1)
B1
---
---, B1…B10 (****)
---
Type of discharge temperature probe, compressor 1 (line 1)
4-20mA
---
---
NTC - PT1000 - 0-1V - 0-10V-
4-20mA - 0-5V - HTNTC
--- (display only)
Discharge temperature value, compressor 1 (line 1)
---
…
… (**)
Upper value
Maximum discharge temperature value, compressor 1 (line 1)
30.0 barg
…
… (**)
Lower value
Minimum discharge temperature value, compressor 1 (line 1)
0.0 barg
…
… (**)
Calibration
Discharge temperature probe calibration, compressor 1 (line 1)
0.0 barg
…
… (**)
…
…
…
…
…
…
Ecaa12
DO
Economizer valve DO position, compressor 6 (line 1)
…
---
---, 01…29 (****)
Status (display only)
Economizer valve DO status, compressor 6 (line 1)
---
---
Closed / Open
Logic
Economizer valve DO logic, compressor 6 (line 1)
NO
---
NC / NO
Function (display only)
Economizer valve function status, compressor 6 (line 1)
---
---
Not active / Active
Ecab04 (*)
Economizer
Enable economizer function (line 1)
NO
---
NO / YES
Compr.Power Thr.
Capacity percentage threshold for economizer activation (line 1)
0
%
0…100
Press.Lim.
Condensing temperature threshold for economizer activation (line 1)
0.0 °C
…
-999.9…999.9
Disch.T.Thr.
Discharge temperature threshold for economizer activation (line 1)
0.0 °C
…
-999.9…999.9