67
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Egaa02
DO
ChillBooster DO position (line 1)
…
---
---, 01…29 (****)
Status (display only)
Status of ChillBooster DO (line 1)
---
---
Closed / Open
Logic
Logic of ChillBooster DO (line 1)
NO
---
NC / NO
Function (display only)
Status of ChillBooster function (line 1)
---
---
Not active / Active
Egab01
Device present
Enable ChillBooster function (line 1)
NO
---
NO / YES
Deactivation when fan-
spower falls under
Fan capacity under which ChillBooster is deactivated (line 1)
95
%
0…100
Egab02
Before the activation fans
at max for
Fans work at maximum capacity at least for this time before
ChillBooster activation (line 1)
5
min
0 to 300
Ext.Temp.Thr.
Outside temperature threshold for ChillBooster activation (line 1)
30.0 °C
…
… (**)
Egab03
Sanitary proc.
Enable hygiene procedure (line 1)
Disab.
---
DISABLE / ENABLE
start at
Hygiene procedure starting time (line 1)
00:00
---
…
Duration
Hygiene procedure duration (line 1)
0
min
0 to 30
Ext.temp.thr
Outside temperature threshold for hygiene procedure activati. (line 1)
5,0 °C
…
… (**)
Egab04
ChillBooster requires
maintenance after
ChillBooster maximum running time (line 1)
200
h
0…999
Reset maintenance time
ChillBooster maintenance time reset (line 1)
NO
---
NO / YES
Ehb01
Avoid simultaneous
pulses betw.lines
Enable simultaneous compressor start up inhibition
NO
---
NO / YES
Delay
Delay between start up for compressors on diff erent lines
0
s
0…999
Ehb03
Force off L2 Comp.s for
line 1 fault
Enable line 2 compressor switch OFF due to line 1 compressor fault
NO
---
NO / YES
Delay
Delay for line 2 compressor switch off after serious alarm on line 1
compressors
0
s
0…999
Ehb04
Switch on L1 Comp.s for
L2 activation
Enable line 1 compressor switch ON due to line 2 compressor
switch ON
NO
---
NO / YES
Switch on period
Delay for line1 compressor switch on for line 2 compressor switch on
30
s
0…999
Force off line 2 if line 1
is off
Enable line 2 compressor switch OFF due to line 1 switch OFF
NO
---
NO / YES
Ehb05
Enable min threshold for
L1 activation
Enable L1 activation by DSS only when suction pressure is greater than
a minimum threshold
NO
---
NO / YES
Threshold
Minimum threshold for line 1 activation by DSS
---
…
… (**)
Eia02
Setpoint SH
PID control set point (valve 1)
11.0
K
-40.0…180.0
LowSH thres.
Low superheat protection threshold (valve 1)
5.0
K
-40.0…180.0
LOP thresh.
Low operating pressure protection threshold (valve 1)
-50.0
---
-60.0… 200.0
MOP thresh.
Maximum operating pressure protection threshold (valve 1)
50.0
---
-60.0… 200.0
Eia04
Setpoint SH
PID control set point (valve 2)
11.0
K
-40.0…180.0
LowSH thres.
Low superheat protection threshold (valve 2)
5.0
K
-40.0…180.0
LOP thresh.
Low operating pressure protection threshold (valve 2)
-50.0
---
-60.0… 200.0
MOP thresh.
Maximum operating pressure protection threshold (valve 2)
50.0
---
-60.0… 200.0
Eib02
Enable manual
Valve position
Enable manual positioning (valve 1)
NO
NO/YES
Manual valve position:
Manual position (valve 1)
0
---
Min / Max
Eib04
Enable manual
Valve position
Enable manual positioning (valve 2)
NO
NO/YES
Manual valve position:
Manual position (valve 2)
0
---
Min / Max
Eic02
S1 off set
Probe S1 reading off set (valve 1)
0.0
Barg/psig
S1 probe (display)
Value read by probe S1 (valve 1)
---
Barg/psig
S2 off set
Probe S2 reading off set (valve 1)
0.0
°C/°F
S2 probe (display)
Value read by probe S2 (valve 1)
---
°C/°F
Eic03
S3 off set
Probe S3 reading off set (valve 1)
0.0
Barg/psig
S3 probe (display)
Value read by probe S3 (valve 1)
---
Barg/psig
S4 off set
Probe S4 reading off set (valve 1)
0.0
°C/°F
S4 probe (display)
Value read by probe S4 (valve 1)
---
°C/°F
Eic04
Alarm:
Abilita l’allarme sonda S1 ( valvola 1 )
EN.
EN./DIS.
Type:
Type of probe S1 (valve 1)
4-20mA
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Min.:
Minimum probe S1 reading (valve 1)
-1.0
Barg/pisg -20.0...200.0
Max.:
Maximum probe S1 reading (valve 1)
9.3
Barg/pisg -20.0...200.0
Alarm min.:
Minimum probe S1 alarm threshold (valve 1)
-1.0
Barg/pisg -20.0...200.0
Alarm max.:
Maximum probe S1 alarm threshold (valve 1)
9.3
Barg/pisg -20.0...200.0
Eic05
Alarm:
Enable probe S2 alarm (valve 1 )
EN.
EN./DIS.
Type:
Type of probe S2 (valve 1)
CAREL NTC
CAREL NTC / 0-10V EXT. SI-
GNAL / NTC SPKP**T0 / CAREL
NTC-HT
Alarm min.:
Minimum probe S2 alarm threshold (valve 1)
-50.0
°C/°F
-60.0...200.0
Alarm max.:
Maximum probe S2 alarm threshold (valve 1)
105.0
°C/°F
-60.0...200.0
Eic06
Alarm:
Enable probe S3 alarm (valve 1)
EN.
EN./DIS.
Type:
Type of probe S3 (valve 1)
4-20mA
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Min.:
Minimum probe S3 reading (valve 1)
-1.0
Barg/pisg -20.0...200.0
Max.:
Maximum probe S3 reading (valve 1)
30.0
Barg/pisg -20.0...200.0
Alarm min.:
Minimum probe S3 alarm threshold (valve 1)
-1.0
Barg/pisg -20.0...200.0
Alarm max.:
Maximum probe S3 alarm threshold (valve 1)
30.0
Barg/pisg -20.0...200.0
Eic07
Alarm:
Enable probe S4 alarm (valve 1)
EN.
EN./DIS.
Type:
Type of probe S4 (valve 1)
CAREL NTC
CAREL NTC / NTC SPKP**T0 /
CAREL NTC-HT
Alarm min.:
Minimum probe S4 alarm threshold (valve 1)
-50.0
°C/°F
-60.0...200.0
Alarm max.:
Maximum probe S4 alarm threshold (valve 1)
105.0
°C/°F
-60.0...200.0