72
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Gba04
Enable ChillBooster as fi rst
prevent step
Enable ChillBooster as fi rst stage for condensing HP prevent (line 1)
NO
---
NO / YES
Off set Chill.
Off set between ChillBooster and prevent setpoint (line 1)
0.0 barg
…
0.0 to 99.9
Gba05
Prevent max.num
Maximum number of prevent allowed before locking compressor (line 1) 3
---
1…5
Prevent max.number
evaluation time
Prevent maximum number evaluation time
60
h
0…999
Reset automatic prevent
Reset number of prevent (line 1)
NO
---
NO / YES
Gba07
Max.num prevent
Maximum number of prevent allowed before locking compressor (line
1, auxiliary regulation)
3
---
1…5
Tempo di valutaz.num.
max prevent
Prevent maximum number evaluation time (auxiliary regulation)
60
h
0…999
Riabilita prevent auto-
matico
Reset number of prevent (line 1, auxiliary regulation)
NO
---
NO / SI
Gba08
Threshold:
Threshold for low pressure prevent with auxiliary regulation
0.5
Barg/
psig
-1.0…150.0
Band:
Diff erential for the prevent re-enter
0.1
Barg/
psig
0.0…60.0
Minimum Power request: Minimum power request in prevent
20.0
%
0.0…100.0
Gba09
Align Pow.Req at the end
of prevent
At the end of prevent action power requst is calculated starting from
the last request value and not from the value available before the
prevent action
NO
NO / YES
Use Suction UoM
Unit selection for prevent threshold and diff erential
NO
NO / YES
Gca01
Common HP type
Type of reset for common HP alarm (line 1)
AUTO
---
AUTO / MAN
Common HP delay
Common high pressure delay (line 1)
10
s
0…999
Gca02
Common LP start delay
Low common condensing pressure delay at start up (line 1)
60
s
0…999
Common LP delay
Low common condensing pressure delay during operation (line 1)
20
s
0…999
Gca03
Time of semi-automatic
alarm evaluation
Period of LP evaluation (line 1)
120
min
0…999
N° of reties before alarm
becomes manual
Number of LP in period after which the alarm becomes manual
(line 1)
5
---
0…999
Gca04
Liquid alarm delay
Liquid level alarm delay (line 1)
0
s
0…999
Oil alarm delay
Common oil alarm delay (line 1)
0
s
0…999
Gca05
Output alarms relays
activation with
Select alarm relay output activation for active alarms or alarms not reset Active
alarms
Active alarms
Alarms not reset
The following parameters refer to line 2, for details see the corresponding parameters for line 1 above
Gbb01
Prevent enable
Enable condensing pressure prevent (line 2)
NO
---
NO / YES
…
…
…
…
…
…
Gcb01
Common HP type
Type of reset for common HP alarm (line 2)
AUTO
---
AUTO / MAN
Common HP delay
Common high pressure delay (line 2)
10
s
0…999
…
…
…
…
…
…
Mask index
Display description
Description
Default
UOM
Values
H.Info
H01
(display only)
Ver.
Software version and date
…
---
…
Bios
Bios version and date
…
---
…
Boot
Boot version and date
…
---
…
H02
(display only)
Board type
Type of hardware
…
---
…
Board size
Hardware size
…
---
…
Total fl ash
Flash memory size
---
kB
…
RAM
RAM size
---
kB
…
Built-In type
Type of built-in display
---
---
None / PGD1
Main cycle
Number of cycles per second and software cycle time
---
cycles/s
ms
…
Mask index
Display description
Description
Default
UOM
Values
I.Setup
Ia01
Pre-confi guration
Pre-confi guration selected
01. RS2
---
--NOT USED—
01. RS2
02. RS3
03. RS3p
04. RS3i
05. RS4
06. RS4i
07. SL3d
08. SL5d
09. SW1
10. SW2
11. SW3
12. d-RS2
13. d-RS3
14. d-RS4
Ia02 (disp. only)
Boards necessary
pLAN boards required for the selected pre-confi guration
---
---
---
Ia03 (disp. only)
Suction line
Number of suction lines featured in the pre-confi guration
---
---
0 to 2
Condenser line
Number of condenser lines featured in the pre-confi guration
---
---
0 to 2
Ia04 (display only)
Num.Comp. L1
Number of compressors featured in the pre-confi guration (line 1)
…
---
1…12
Comp.type L1
Type of compressors featured in the pre-confi guration (line 1)
RECIPROCATING ---
RECIPROCATING / SCROLL
SCREW
Num.Comp. L2
Number of compressors featured in the pre-confi guration (line 2)
…
---
1…12
Comp.type L2
Type of compressors featured in the pre-confi guration (line 2)
RECIPROCATING ---
RECIPROCATING / SCROLL
Ia05 (display only)
Num.alarms per comp.
Number of alarms for compressor featured in the pre-confi guration
1/4 (*)
---
0 to 4/7 (*)
Cond.Gen.Alarm
Enable common condenser alarm
EN
---
EN/DIS
HP comm.pressostat
Enable common HP pressure switch
EN
---
EN/DIS
LP comm.pressostat
Enable common LP pressure switch
EN
---
EN/DIS
Ib01
Type of Installation
Type of system
S
CONDENSER
---
SUCTION / CONDENSER
S CONDENSER
Ib02
Measure Units
Unit of measure
°C/barg
---
°C/barg / °F/psig
Summary of Contents for PRK300D0E0