66
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Efa09
High alarm
High alarm enabling for generic stage function 1
DISAB.
---
DISABLE / ENABLE
High alarm
High alarm threshold for generic stage function 1
0.0 °C
…
… (**)
Delay time
High alarm delay for generic stage function 1
0
s
0…9999
Alarm type
Low alarm enabling for generic stage function 1
LIGHT
---
LIGHT / SERIOUS
Low alarm
Low alarm threshold for generic stage function 1
DISAB.
---
DISABLE / ENABLE
Low alarm
Low alarm delay for generic stage function 1
0.0 °C
…
… (**)
Delay time
Low alarm delay for generic stage function 1
0
s
0…9999
Alarm type
Type of low alarm for generic stage function 1
LIGHT
---
LIGHT / SERIOUS
…
…
…
…
…
…
Efb05
Gen.Modulat.1
Enable generic modulating function 1 management
DISAB.
---
DISABLE / ENABLE
Gen.Modulat.2
Enable generic modulating function 2 management
DISAB.
---
DISABLE / ENABLE
Efb06
Regulation variable
Control variable for generic modulating function 1
---
---
…
Mode
Direct or reverse modulation
DIRECT
---
DIRECT / REVERSE
Efb07
Enable
Enabling variable for generic modulating function 1
---
---
…
Description
Enable description change
SKIP
---
SKIP / CHANGE
---------------
Description
---
---
…
Efb08
Setpoint
Setpoint for generic modulating function 1
0.0 °C
…
… (**)
Diff erential
Diff erential for generic modulating function 1
0.0 °C
…
… (**)
Efb09
High alarm
High alarm enabling for generic modulating function 1
DISAB.
---
DISABLE / ENABLE
High alarm
High alarm threshold for generic modulating function 1
0.0 °C
…
… (**)
Delay time
High alarm delay for generic modulating function 1
0
s
0…9999
Alarm type
Low alarm enabling for generic modulating function 1
LIGHT
---
LIGHT / SERIOUS
Efb010
Out upper limit
Output upper limit for generic modulating function 1
100.0
%
0…100
Out lower limit
Output lower limit for generic modulating function 1
0.0
%
0…100
Enable cutoff
Enable cut off function for generic modulating function 1
NO
---
NO / YES
Cutoff diff .
Cut off diff erential for generic modulating function 1
0.0 °C
…
… (**)
Cutoff hys.
Cut off hysteresis for generic modulating function 1
0.0 °C
…
… (**)
Efb20
Low alarm
Low alarm enabling for generic modulating function 1
DISAB.
---
DISABLE / ENABLE
Low alarm
Low alarm threshold for generic modulating function 1
0.0 °C
…
… (**)
Delay time
Low alarm delay for generic modulating function 1
0
s
0…9999
Alarm type
Low alarm type for generic modulating function 1
LIGHT
---
LIGHT / SERIOUS
…
…
…
…
…
…
Efc05
Gen.alarm 1
Enable generic alarm function 1 management
DISAB.
---
DISABLE / ENABLE
Gen.alarm 2
Enable generic alarm function 2 management
DISAB.
---
DISABLE / ENABLE
Efc06
Regulation variable
Monitored variable for generic alarm function 1
---
---
…
Enable
Enabling variable for generic alarm function 1
---
---
…
Description
Enable description change
SKIP
---
SKIP / CHANGE
---------------
Description
---
---
…
Efc07
Alarm type
Alarm type for generic alarm function 1
LIGHT
---
LIGHT / SERIOUS
Delay time
Delay for generic alarm function 1
0
s
0…9999
…
…
…
…
…
…
Efd05
Generic Function Sche-
duler
Enable generic scheduler function
DISAB.
---
DISABLE / ENABLE
Gen.funct.scheduling
connected to global
scheduling
Generic scheduler function considers the same special days and periods
of global scheduler
NO
---
NO / YES
Efd06
Enable
Enabling variable for generic scheduler function
---
---
…
Efd07
Activ.Time Bands
Day of the week
---
---
MON, ..., SUN
TB1: --:-- -> --:--
Time band 1 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
…
…
…
…
…
…
…
TB4: --:-- -> --:--
Time band 4 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
…
…
Changes
Time band changes action
---
---
---
CONFIRM&SAVE
LOAD PREVIOUS
CLEAR ALL
Copy to
Copy settings to other days
0
---
MONDAY…SUNDAY; MON-FRI;
MON-SAT; SAT&SUN; ALL DAYS
Efe05
Gen.A Measure
Generic analogue input A unit of measure selection
°C
---
°C; °F; barg; psig; %; ppm -
…
…
…
…
…
Efe06/Efe07 (**)
---
Generic probe A position
B1
---
---, B1…B10 (****)
---
Generic probe A type
4-20mA
---
… (**)
--- (display only)
Generic probe A value
---
…
… (**)
Upper value
Generic probe A max. limit
30.0 barg
…
… (**)
Lower value
Generic probe A min. limit
0.0 barg
…
… (**)
Calibration
Generic probe A adjustment
0.0 barg
…
… (**)
…
...
...
…
…
…
Efe16
DI
Generic digital input F DI position
---
---
---, 01…18, B1…B10 (****)
Status (display only)
Status of generic digital input F DI
---
---
Closed / Open
Logic
Logic of generic digital input F DI
NC
---
NC / NO
Function (display only)
Status of generic digital input F DI
---
---
Not active / Active
…
...
...
…
…
…
Efe21
DO
Generic stage 1 DO position
…
---
---, 01…29 (****)
Status (display only)
Status of generic stage 1 DO
---
---
Closed / Open
Logic
Logic of generic stage 1 DO
NO
---
NC / NO
Function (display only)
Generic stage 1 DO function status
---
---
Not active / Active
…
…
…
…
…
…
Efe29
Modulating.1
Generic modulating 1 AO position
0
---
---, 01…06 (****)
Type (****)
Type of output, PWM / phase control for generic modulating function
1 AO (line 1)
FCS1*-CON-
VONOFF
---
FCS1*-CONVONOFF; "-----";"
MCHRTF*";" FCS3*-CONV010"
Status (display only)
Generic modulating 1 output value
0
%
0.0…100.0
…
…
…
…
…
…
Egaa01
DI
ChillBooster fault DI position (line 1)
---
---
---, 01…18, B1…B10 (****)
Status (display only)
Status of ChillBooster fault DI (line 1)
---
---
Closed / Open
Logic
Logic of ChillBooster fault DI (line 1)
NC
---
NC / NO
Function (display only)
Status of ChillBooster fault (line 1)
---
---
Not active / Active