71
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
…
…
…
…
…
…
Egbb01
Device present
ChillBooster function enable (line 2)
NO
---
NO / YES
Deactivation when fan-
spower falls under
Fans capacity under which ChillBooster is deactivated (line 2)
95
%
0…100
…
…
…
…
…
…
Mask index
Display description
Description
Default
UOM
Values
F.settings
Faaa01
Summer/Winter
Enable Summer/Winter period management (line 1)
NO
---
NO / YES
Special days
Enable special days management (line 1)
NO
---
NO / YES
Holiday periods
Enable holiday period management (line 1)
NO
---
NO / YES
Faaa02
Begin
Summer period beginning date (line 1)
---
---
01/Gen…31/Dic
End
Summer period end date (line 1)
---
---
01/Gen…31/Dic
Faaa03
Day 01
Special day 1 date (line 1)
---
---
01/Gen…31/Dic
…
…
…
…
…
…
Faaa04
Day 10
Special day 10 date (line 1)
---
---
01/Gen…31/Dic
Faaa05
P1
Holiday period P1 beginning date (line 1)
---
---
01/Gen…31/Dic
---
Holiday period P1 end date (line 1)
---
---
01/Gen…31/Dic
…
…
…
…
…
P5
Holiday period P5 beginning date (line 1)
---
---
01/Gen…31/Dic
---
Holiday period P5 end date (line 1)
---
---
01/Gen…31/Dic
Faab01
Date format
Date format
DD/MM/YY ---
----
DD/MM/YY
MM/DD/YY
YY/MM/DD
Faab02/Faab03/
Faab04
Hour
Hour and minute
…
…
…
Date
Date
… …
…
Day (display only)
Day of the week calculated from current date
…
…
Monday… Sunday
Faab05
Daily saving time
Enable daylight saving time
DISABLE
---
DISABLE / ENABLE
Transition time
Off set time
60
---
0 to 240
Start, ...
Starting week, day and month and hour for daylight saving time
…
…
…
End, ...
End week, day and month and hour for daylight saving time
…
…
…
Fb01
Language
Current language
ENGLISH
---
…
Fb02
Disable language mask at
start-up
Disable the change language screen at start-up
YES
---
NO / YES
Countdown
Starting value for countdown, time change language screen active.
60
s
0…60
Fb03
Main mask selection
Main screen selection
LINE 1
---
LINE 1 / LINE 2
DOUBLE SUCTION
DOUBLE CONDENSER
Fca01
Address
Address of the controller in a supervisory system network (line 1)
196
---
0 to 207
Protocol
Supervisor communication protocol (line 1)
pRACK
MANAGER
---
--
CAREL SLAVE LOCAL
CAREL SLAVE REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
Baudrate
Supervisor communication baud rate (line 1)
19200
---
1200 to 19200
Fca02
Address
Address of the controller in a supervisory system network (line 1)
1
---
0…207
Protocol
Supervisor communication protocol (line 1)
CAREL
---
---
CAREL SLAVE LOCAL
MODBUS SLAVE
pRACK MANAGER
Baudrate
Supervisor communication baud rate (line 1)
19200
---
1200…19200
Fd01
Insert password
Password
0000
---
0…9999
Logged as (display only)
Current password level
---
---
User, Service, Manufacturer
Fd02
Logout
Logout
NO
---
NO / YES
Fd03
User
User password
0000
---
0…9999
Service
Service password
1234
---
0…9999
Manufacturer
Manufacturer password
1234
---
0…9999
The following parameters refer to line 2, for details see the corresponding parameters for line 1 above
Fcb01
Address
Enable summer/winter period management (line 2)
196
---
0 to 207
Protocol
Enable special days management (line 2)
pRACK
MANAGER
---
--
CAREL SLAVE LOCAL
CAREL SLAVE REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
Baudrate
Enable holiday period management (line 2)
19200
---
1200 to 19200
Fcb01
Address
Enable summer/winter period management (line 2)
1
---
0…207
Protocol
Enable special days management (line 2)
MODBUS
SLAVE
---
---
CAREL SLAVE LOCAL
MODBUS SLAVE
pRACK MANAGER
Baudrate
Enable holiday period management (line 2)
19200
---
1200…19200
Mask index
Display description
Description
Default
UOM
Values
G.Safety
Gba01
Prevent enable
Enable condensing pressure prevent (line 1)
NO
---
NO / YES
Gba02
Setpoint
Condensing pressure prevent threshold (line 1)
0.0 barg
…
… (**)
Diff erential
Condensing pressure prevent diff erential (line 1)
0.0 barg
…
0.0 to 99.9
Decrease compressor
power time
Decreasing capacity time (line 1)
0
s
0…999
Gba03
Enable Heat Reclaim as
fi rst prevent step
Enabling heat recovery as fi rst stage for condensing HP prevent
(line 1)
NO
---
NO / YES
Off set HeatR.
Off set between heat recovery and prevent setpoint (line 1)
0.0 barg
…
0.0 to 99.9
Summary of Contents for PRK300D0E0