56
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Ac02
L1:
L2:
Unit status (display only)
Off from
keypad
---
…(See above Ac01)
---
On-Off from keypad (line 1)
OFF
---
OFF / ON
---
On-Off from keypad (line 2)
OFF
---
OFF / ON
Ac03
Enable of unit OnOff
By digit input
Enable unit On/Off from digit input (line 1)
NO
---
NO / YES
By supervisor
Enable unit On/Off from supervisor (line 1)
NO
---
NO / YES
By black out
Enable unit On/Off from black out (line 1)
NO
---
NO / YES
Ac04
Unit on delay after
blackout
System on delay after black out (line 1)
0
s
0…999
Ac06
Enable of unit OnOff
By digit input
Enable unit On/Off from digit input (line 2)
NO
---
NO / YES
By supervisor
Enable unit On/Off from supervisor (line 2)
NO
---
NO / YES
By black out
Enable unit On/Off from black out (line 2)
NO
---
NO / YES
Ac07
Unit on delay after
blackout
System on delay after black out (line 2)
0
s
0…999
Mask index
Display Description
Description
Default
UOM
Values
B.Input./output
(the I/Os available depend on the selected confi guration, the following are just some examples. For the complete list of I/O positions availa-
ble see Appendix A.5)
Baa02
DI
Alarm 1 for compressor 1 DI position (line 1)
03
---
---, 01…18, B1…B10 (****)
Status (display only)
Status of alarm 1 for compressor 1 DI (line 1)
---
---
Closed
Open
Logic
Logic of alarm 1 for compressor 1 DI (line 1)
NC
---
NC / NO
Function (display only)
Alarm 1 for compressor 1 function status (line 1)
---
---
Not active / Active
…
…
…
…
…
…
Bab01
---
Suction pressure probe position (line1)
B1
---
---, B1…B10 (****)
---
Suct pressure probe type (line 1)
4-20mA
---
----
0-1V - 0-10V- 4-20mA- 0-5V
--- (display only)
Suction pressure value (line 1)
---
…
… (**)
Upper value
Suct pressure maximum value (line 1)
7,0 barg
…
… (**)
Lower value
Suct pressure minimum value (line 1)
-0,5 barg
…
… (**)
Calibration
Suction pressure probe adjustment (line 1)
0.0 barg
…
… (**)
…
…
…
…
…
…
Bac02
Line relay DO
Compressor 1 line DO position and status (On/Off ) display (line 1)
…
---
---, 01…29 (****)
Part winding DO/Star
relay DO (*)
Compressor 1 part winding or star DO position and status (On/Off )
display (line 1)
…
---
---, 01…29 (****)
---/ Delta relay DO (*)
Compressor 1 delta DO position and status (On/Off ) display (line 1)
…
---
---, 01…29 (****)
Logic
DO logic to start compressor 1 (line 1)
NC
---
NC / NO
Bac03
DO
Compressor 1 unloader 1 DO position (line 1)
…
---
---, 01…29 (****)
Status (display only)
Status for compressor 1 unloader 1 DO (line 1)
---
---
Closed / Open
Logic
Logic for compressor 1 unloader 1 DO (line 1)
NO
---
NC / NO
Function (display only)
Compressor 1 unloader 1 function status (line 1)
---
---
Not active / Active
…
…
…
…
…
…
Bad01
AO
Compressor modulating device AO position (line 1)
0
---
---, 01…06 (****)
Type (****)
Type of output, PWM / phase control for compressor modulating device
(line 1)
FCS1*-CON-
VONOFF
---
----
FCS1*-CONVONOFF
FCS3*-CONV010"
Status (display only)
Modulating device output value (line 1)
0
%
0.0 to 100.0
…
…
…
…
…
…
Bb01
Suction L1
Suction line 1 in manual mode
DIS
---
DIS / EN
Suction L2
Suction line 2 in manual mode
DIS
---
DIS / EN
Discharge L1
Condenser line 1 in manual mode
DIS
---
DIS / EN
Discharge L2
Condenser line 2 in manual mode
DIS
---
DIS / EN
Timeout
Manual mode duration after last key pressed
10
min
0…500
Bba02
Compressor 1
Force to
Manual stages request for compressor 1 (line 1)
OFF
---
OFF / ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
…
…
…
…
…
…
Bba16
Compressor 12
Force to
Manual stage request for compressor 12 (line 1)
OFF
---
OFF / ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
Bba17
Oil cool pump1
Force to
Manual operating status for oil cooling pump 1 (line 1)
OFF
---
OFF / ON
Oil cool pump2
Force to
Manual operating status for oil cooling pump 2 (line 1)
OFF
---
OFF / ON
Bba18
Oil cool fan
Force to
Manual operating status for oil cooling fan (line 1)
OFF
---
OFF / ON
Bba20
Compressor 1
Force to
Manual stage request for compressor 1 (line 2)
OFF
---
OFF / ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
…
…
…
…
…
Bba34
Compressor 12
Force to
Manual stage request for compressor 12 (line 2)
OFF
---
OFF / ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
Bba35
Oil cool pump1
Force to
Manual operating status for oil cooling pump 1 (line 2)
OFF
---
OFF / ON
Oil cool pump2
Force to
Manual operating status for oil cooling pump 2 (line 2)
OFF
---
OFF / ON
Bba37
Oil cool fan
Force to
Manual operating status for oil cooling fan (line 2)
OFF
---
OFF / ON
Bba38
Fan1
force
Manual operating status for fan 1 (line 1)
OFF
---
OFF / ON
…
…
…
…
…
…
Bba53
Fan16
force
Manual operating status for fan 16 (line 1)
OFF
---
OFF / ON