ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Daa21
DO
Fan 1 DO position (line 1)
03
---
---, 01…29 (****)
Status (display only)
Status of fan 1 DO (line 1)
---
---
Closed / Open
Logic
Logic of fan 1 DO (line 1)
NC
---
NC / NO
Function (display only)
Fan 1 function status (line 1)
---
---
Not active / Active
…
…
…
…
…
…
Daa38
AO
Inverter fan AO position (line 1)
0
---
---, 01…06 (****)
Type (****)
Type of output, PWM / phase control per AO fan inverters (line 1)
FCS1*-CON-
VONOFF
---
FCS1*-CONVONOFF; " -----";"
MCHRTF*";" FCS3*-CONV010"
Status (display only)
Inverter fan output value (line 1)
0
%
0.0…100.0
…
…
…
…
…
…
Dab01
Regulation by
Condenser control by temperature or pressure (line 1)
PRESSURE
---
PRESSURE/TEMPERATURE
Regulation type
Condenser control type (line 1)
PROPORTI.
BAND
---
PROPORTIONAL BAND
NEUTRAL ZONE
Dab02
Minimum
Condenser setpoint lower limit (line 1)
… (**)
…
… (**)
Maximum
Condensers setpoint higher limit (line 1)
… (**)
…
… (**)
Dab03
Setpoint
Condenser setpoint (line 1)
… (**)
…
… (**)
Dab04
Fans work only when at
least one compressor
works
Enable fan operation linked to compressor operation
NO
---
NO / YES
Dab05
Cut_Off enable
Enable fan cut-off function
NO
---
NO / YES
Cut-Off request
Cut-off value
0.0
%
0.0…100.0
Diff .
Cut-off diff erential
… (**)
…
… (**)
Hysteresis
Cut-off hysteresis
… (**)
…
… (**)
Dab6/ Dab8 (**)
Reg.type
Type for proportional control (condenser line 1)
PROP.
---
PROP.
PROP.+INT.
Integral time
Integral time for prop. control (cond. line 1)
300
s
0…999
Dab7/ Dab9 (**)
Diff erential
Diff erential for proportional control (cond. line 1)
… (**)
…
… (**)
Dab10/Dab11
(**)
NZ diff .
Neutral zone control diff erential (line 1)
… (**)
…
… (**)
Activ.diff .
Neutral zone control diff erential for device activation (line 1)
… (**)
…
… (**)
Deact.diff .
Neutral zone control diff erential for device deactivation (line 1)
… (**)
…
… (**)
Dab12/Dab13
(**)
En.force off power
Enable capacity immediate decreasing to 0 (line 1)
NO
---
NO / YES
Setp.for force off
Threshold for capacity decreasing to 0 (line 1)
… (**)
…
… (**)
Dab14
Power load to 100% min
time
Minimum time to increase capacity request to 100%, Neutral zone
control (condenser line 1)
15
s
0…9999
Power load to 100% max
time
Maximum time to increase capacity request to 100%, Neutral zone
control (condenser line 1)
90
s
0…9999
Dab15
Power unload to 0% min
time
Minimum time to decrease capacity request to 0%, Neutral zone control
(condenser line 1)
30
s
0…9999
Power unload to 0% max
time
Maximum time to decrease capacity request to 0%, Neutral zone control
(condenser line 1)
180
s
0…9999
Dad01
Enable condensing
setpoint compensation
Enable setpoint compensation (condenser line 1)
NO
---
NO / YES
Dad02
Winter off set
Enable setpoint compensation (condenser line 1)
0.0
…
-999.9…999.9
Closing off set
Off set applied for Winter period
0.0
…
-999.9…999.9
Dad03
Enable setpoint compen-
sation by scheduler
Enable scheduler setpoint compensation (condenser line 1)
NO
---
NO / YES
Dad04
Activ.Time Bands
Day of the week
---
---
MON, ...SUN
TB1: --:-- -> --:--
Time band 1 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
…
…
…
…
…
…
…
TB4: --:-- -> --:--
Time band 4 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
…
…
Changes
Time band changes action
---
---
---
CONFIRM&SAVE
LOAD PREVIOUS
CLEAR ALL
Copy to
Copy settings to other days
0
---
MONDAY…SUNDAY; MON-FRI;
MON-SAT; SAT&SUN; ALL DAYS
Dad05
Enable fl oating conden-
sing setpoint
Enable fl oating setpoint (condenser line 1)
NO
---
NO / YES
Dad06
Off set for external tem-
perature
Temperature delta for fl oating setpoint (condenser line 1)
0.0
…
-9.9…9.9
Controlled by:
-Digital input
Enable fl oating condensing from digital input
NO
---
NO / YES
Dad07
Change set by digital
input
Enable setpoint compensation by digital input (suction/condensing
line 1)
NO
---
NO / YES
Dae01
Cond.pressure/tempera-
ture high alarm
Type of high condensing pressure/temperature alarm threshold (line 1) ABSOLUTE
---
ABSOLUTE / RELATIVE
Threshold
High condensing pressure/temperature alarm threshold (line 1)
24.0 barg
…
… (**)
Dae02
Cond.pressure/tempera-
ture alarm diff .
High condensing pressure/temperature alarm diff erential (line 1)
1.0 barg
…
… (**)
Alarm delay
High condensing pressure/temperature alarm delay (line 1)
60
s
0…999
Dae03
Cond.pressure/tempera-
ture low alarm
Type of low condensing pressure/temperature alarm threshold
(line 1)
ABSOLUTE
---
ABSOLUTE / RELATIVE
Threshold
Low condensing pressure/temperature alarm threshold (line 1)
7.0 barg
…
… (**)
Dae04
Cond.pressure/tempera-
ture alarm diff .
Low condensing pressure/temperature alarm diff erential (line 1)
1.0 barg
…
… (**)
Alarm delay
Low condensing pressure/temperature alarm delay (line 1)
30
s
0…999
Dae05
Common fan overload
Common fan overload (line 1)
YES
---
NO / YES
Delay
Common fan overload alarm activation delay
AUTOMATIC ---
AUTOMATIC / MANUAL
Reset
Type of common fan overload alarm reset
0
s
0 to 500
Daf01
Number of present fans
Number of fans (line 1)
3
---
0 to 16
Daf02
Fan1, Fan2, …
Enable fans 1 to 12 (line 1)
EN
---
DIS / EN
Daf03
Fan13, Fan14, …
Enable fans 13 to 16 (line 1)
EN
---
DIS / EN