pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Caf92
S1
Enable stages and stages for compressor group 1 (line 1)
YES
100
---
%
NO/YES
100; 50/100; 50/75/100;
25/50/75/100; 33/66/100
…
…
…
…
…
S4
Enable stages and stages for compressor group 4 (line 1))
NO
---
---
kW
NO / YES
S1…S4
Caf93
C01
Size group for compressor 1 (line 1) or presence of inverter
S1
---
S1…S4/INV
…
…
…
…
…
C12
Size group for compressor 6 (line 1)
S1
---
S1…S4
Caf95
Min on time
Minimum Digital Scroll
TM
compressor On time (line 1)
60
s
0…999
Min off time
Minimum Digital Scroll
TM
compressor Off time(line 1)
180
s
0…999
Min time to start same
compressor
Minimum time between starts for Digital Scroll
TM
compressor (line 1)
360
s
0…999
Reactivate start-up
procedure after
Digital Scroll
TM
compressor start-up procedure reactivation time (line 1)
480
min
0…9999
Cag01
Minimum voltage
Voltage corresponding to the minimum capacity of the inverter (line 1)
0.0
V
0.0…10.0
Maximum voltage
Voltage corresponding to the maximum capacity of the inverter (line 1)
10.0
V
0.0…10.0
Nominal freq.
Nominal frequency (nominal capacity at nominal frequency) (line 1)
50
Hz
0…150
Nominal power
Nominal capacity for compressor managed by inverter at nominal
frequency (line 1)
10.0
kW
0.0…500.0
Cag02
Rising time
Time to pass from min capacity to max capacity for modulat. device (line 1) 90
s
0…600
Falling time
Time to pass from max capacity to min capacity for modul. device (line 1) 30
s
0…600
Cag03
Enable compressor
modulation inside neutral
zone
Enable compressor 1 modulation inside Neutral zone (line 1)
YES
---
NO / YES
Cag04
Enable suction press.
backup probe
Enable screens for suction pressure backup probe confi guration
(line 1)
NO
---
NO / YES
Cag05
Request in case of regulat.
probe fault
Compressor forcing value in case of suction probes fault (line 1)
50.0
%
0.0…100.0
Cag06
Enable anti liquid return
valve
Enable liquid non return function (line 1)
NO
---
NO / YES
Cag07
Enable compressor enve-
lop management (*)
Enable compressor envelope management (screw only).
For details on confi guration contact Carel.
NO
---
NO / YES
The following parameters refer to line 2, for details see the corresponding parameters for line 1 above
Cba01
DI
Alarm 1 for compressor 1 DI position (line 2)
03
---
---, 01…18, B1…B10 (****)
Status (display only)
Status of alarm 1 for compressor 1 DI (line 2)
---
---
Closed / Open
Logic
Logic of alarm 1 for compressor 1 DI (line 2)
NC
---
NC / NO
Function (display only)
Alarm 1 for compressor 1 function status (line 2)
---
---
Not active / Active
…
…
…
…
…
…
Cbb01
Regulation by
Compressor control by temperature or pressure (line 2)
PRESSURE
---
PRESSURE / TEMPERATURE
Regulation type
Compressor control type (line 2)
NEUTRAL
ZONE
---
PROPORTIONAL BAND
NEUTRAL ZONE
…
…
…
…
…
…
Cbc01
Working hours
Compressor 1
Compressor 1 max operating hours (line 2)
---
---
0…999999
…
…
…
…
…
…
Cbd01
Enable suction setpoint
compensation
Enable setpoint compensation (suction line 2)
NO
---
NO / YES
Enable compensation by
analog IN
Enable setpoint compensation by probe (suction line 2)
NO
---
NO / YES
…
…
…
…
…
…
Cbe01
Number of alarms for
each compressor
Number of alarms for each compressor (line 2)
1
---
0 to 4
…
…
…
…
…
…
Cbf02
Compressors type
Type of compressors (line 2)
RECIPROCA-
TING
---
RECIPROCATING
SCROLL
Compressors number
Number of compressors (line 2)
2/3 (*)
---
1…12
…
…
…
…
…
…
Cbg01
Minimum voltage
Voltage corresponding at the minimum capacity of the inverter (line 2)
0.0
Hz
0.0…10.0
Maximum voltage
Voltage corresponding at the maximum capacity of the inverter (line 2)
10.0
Hz
0.0…10.0
Nominal freq.
Nominal frequency (nominal capacity at nominal frequency) (line 2)
50
Hz
0…150
Nominal power
Nominal capacity for compressor managed by inverter at nominal
frequency (line 2)
10.0
kW
0.0…500.0
…
…
…
…
…
…
Mask index
Display description
Description
Default
UOM
Values
D.Condensers
(The I/Os available depend on the selected confi guration, the following are just some examples. For the complete list of I/O positions availa-
ble see Appendix A.5)
Daa01
DI
Fan 1 overload DI position (line 1)
…
---
---, 01…18, B1…B10 (****)
Status (display only)
Status of fan 1 overload DI (line 1)
---
---
Closed / Open
Logic
Logic of fan 1 overload DI (line 1)
NC
---
NC / NO
Function (display only)
Fan 1 overload function status (line 1)
---
---
Not active / Active
…
…
…
…
…
…
Daa39
---
Condenser probe position (line 1)
B1
---
---, B1…B10 (****)
---
Condenser probe type (line 1)
4-20mA
---
----
0-1V
0-10V
4-20mA
0-5V
--- (display only)
Condensing pressure value (line 1)
---
…
…(**)
Max limit
Maximum condensing pressure value (line 1)
30,0 barg
…
…(**)
Min limit
Minimum condensing pressure value (line 1)
0,0 barg
…
…(**)
Calib.
Condensing pressure probe calibration (line 1)
0,0 barg
…
…(**)
…
…
…
…
…
…