63
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Daf04
Refrigerant type
Type of refrigerant (condenser line 1)
R404A
---
R22 - R134a - R404A - R407C -
R410A - R507A - R290 - R600 -
R600a - R717 -R744 - R728 -
R1270 - R417A - R422D -R413A -
R422A - R423A - R407A - R427A
- R245Fa - R407F - R32
Daf05
Devices rotation type
Type of rotation devices (condenser line 1)
FIFO
---
------
FIFO
LIFO
TIME
CUSTOM
Daf07, Daf08
Custom rotation
Switch ON order
Switch ON order for fans with custom rotation (condenser line 1)
1
---
1…16
Daf09, Daf10
Custom rotation
Switch OFF order
Switch OFF order for fans with custom rotation (condenser line 1)
1
---
1…16
Dag01
Modulate speed device
Fan driver type (line 1)
NONE
---
NONE
INVETER
PHASE CONTROL
Type (****)
Type of output, PWM / phase control for condenser modulating device
(line 1)
----
---
----
MCHRTF*
FCS3*-CONV010
Dag02
Neutral zone reg.
Fan control also inside Neutral zone (line 1)
NO
---
NO / YES
Min.out value
Minimum voltage for compressor inverter (line 1)
0.0
V
0.0 to 9.9
Max.out value
Maximum voltage for compressor inverter (line 1)
10.0
V
0.0 to 99.9
Min. power refer.
Minimum capacity of fan modulating device (line 1)
60
%
0…100
Max. power refer.
Maximum capacity of fan modulating device (line 1)
100
%
0…999
Dag03
Rising time
Time to pass from min capacity to max capacity for fan modulating
device (line 1)
1200
s
0 to 32000
Falling time
Time to pass from max capacity to min capacity for fan modulating
device (line 1)
1200
s
0 to 32000
Num.control.fans
Number of fans under inverter (only for alarm enabling)
1
---
0 to 16
Dag04
Split Condenser
Enable split condenser (line 1)
NO
---
NO / YES
Controlled by:
-Digital input
Split Condenser controlled by digital input (line 1)
---
---
NO / YES
-External temp.
Split Condenser controlled by outside temperature (line 1)
---
---
NO / YES
-Scheduler
Split Condenser controlled by scheduler (line 1)
---
---
NO / YES
Dag05
Est. Temp.Thr.
Split condenser by outside temperature management setpoint
(line 1)
10.0 °C
…
-99.9…99.9
Est. Temp.Diff .
Split condenser by outside temperature management diff erential (line 1)
2.5 °C
…
-99.9…99.9
Dag06
Type
Fans enabled with split condenser (line 1)
CUSTOM
---
CUSTOM
ODD
EVEN
GREATER THAN
LESS THAN
---
Only when enabling type is GREATER THAN or LESS THAN, number of
fans to consider for splitting (line 1)
0
---
0 to 16
Dag09
Disable split condenser as
fi rst stage of HP pressostat
Disable split condenser when high condensing pressure prevent occurs
(line 1)
NO
---
NO / YES
for
Duration of split condenser deactivation for high condensing
pressure prevent (line 1)
0
h
0 to 24
Dag10
Anti-noise
Enable silencer (line 1)
DISAB.
---
DISABLE / ENABLE
Max output
Maximum request allowed when silencer function is active (line 1)
75.0 %
%
0.0…100.0
Controlled by:
-Digital input
Silencer controlled by digital input (condenser line 1)
NO
---
NO / YES
-Scheduler
Silencer controlled by scheduler (condenser line 1)
NO
---
NO / YES
Dag12
Activ.Time Bands
Day of the week
---
---
MON, ..., SUN
TB1: --:-- -> --:--
Time band 1 enabling and defi nition: start hour and minute, end hour
and minute (condenser line 1)
---
…
…
…
…
…
…
…
TB4: --:-- -> --:--
Time band 4 enabling and defi nition: start hour and minute, end hour
and minute (condenser line 1)
---
…
…
Changes
Time band changes action
---
---
---
CONFIRM&SAVE
LOAD PREVIOUS
CLEAR ALL
Copy to
Copy settings to other days
0
---
MONDAY…SUNDAY; MON-FRI;
MON-SAT; SAT&SUN; ALL DAYS
Dag13
Speed Up
Enable speed up (condenser line 1)
YES
---
NO / YES
Speed Up time
Speed up time (condenser line 1)
5
s
0…60
Ext.Temp.Manage
Enable speed up management by outside temperature (condenser line 1) DIS
---
DIS / EN
Ext.Temp.Thresh.
Outside temperature threshold for speed up management
(condenser line 1)
25.0 °C
…
-99.9…99.9
Ext.Temp.Diff .
Outside temperature diff erential for speed up management
(condenser line 1)
2.5 °C
…
-99.9…99.9
Dag14
Enable condensing press.
backup probe
Enable the screens for condensing pressure backup probe
confi guration (condenser line 1)
NO
---
NO / YES
Dag15
Request in case of egulat.
probes fault
Value of fans forcing in case of condensing probes fault (line 1)
50.0
%
0.0…100.0
The following parameters refer to line 2, for details see the corresponding parameters for line 1 above
Dba01
DI
Fan 1 overload DI position (line 2)
…
---
---, 01…18, B1…B10 (****)
Status (display only)
Status of fan 1 overload DI (line 2)
---
---
Closed / Open
Logic
Logic of fan 1 overload DI (line 2)
NC
---
NC / NO
Function (display only)
Fan 1 overload function status (line 2)
---
---
Not active
Active
…
…
…
…
…
…