pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index
Display description
Description
Default
UOM
Values
Eic08
ID1 confi guration:
Confi guration of action of digital input 1 on driver (valve 1)
REG. BACKUP
DISABLED / REG. SAFETY / REG.
BACKUP / START/STOP REG. /
VALVE FORCED 100% OPEN /
BATTERY ALARM MNG. / VALVE
REGULATION OPT. AFTER
DEFROST
ID2 confi guration:
Confi guration of action of digital input 2 on driver (valve 1)
DISABLED
DISABLED / REG. SAFETY / REG.
BACKUP / START/STOP REG. /
VALVE FORCED 100% OPEN /
BATTERY ALARM MNG. / VALVE
REGULATION OPT. AFTER
DEFROST
Eic09
DI1:
Digital input 1 status (valve 1)
---
DI2:
Digital input 2 status (valve 1)
---
Eic10
Valve A relay confi g.:
Confi guration of digital output1 (valve 1)
ALARM RELAY
DISABLED / ALARM RELAY
/ SOLENOID VALVE RELAY /
VALVE + ALARM RELAY / RE-
VERSED ALARM RELAY / VALVE
POSITION RELAY
Eic11
Valve B relay confi g.:
Confi guration of digital output 2 (valve 1)
ALARM RELAY
DISABLED / ALARM RELAY
/ SOLENOID VALVE RELAY /
VALVE + ALARM RELAY / RE-
VERSED ALARM RELAY / VALVE
POSITION RELAY
Eic12
S1 off set
Probe S1 reading off set (valve 2)
0.0
Barg/psig
S1 probe (display)
Value read by probe S1 (valve 2)
---
Barg/psig
S2 off set
Probe S2 reading off set (valve 2)
0.0
°C/°F
S2 probe (display)
Value read by probe S2 (valve 2)
---
°C/°F
Eic13
S3 off set
Probe S3 reading off set (valve 2)
0.0
Barg/psig
S3 probe (display)
Value read by probe S3 (valve 2)
---
Barg/psig
S4 off set
Probe S4 reading off set (valve 2)
0.0
°C/°F
S4 probe (display)
Value read by probe S4 (valve 2)
---
°C/°F
Eic14
Alarm:
Enable probe S1 alarm (valve 2)
EN.
EN./DIS.
Type:
Type of probe S1 (valve 2)
4-20mA
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Min.:
Minimum probe S1 reading (valve 2)
-1.0
Barg/pisg -20.0...200.0
Max.:
Maximum probe S1 reading (valve 2)
9.3
Barg/pisg -20.0...200.0
Alarm min.:
Minimum probe S1 alarm threshold (valve 2)
-1.0
Barg/pisg -20.0...200.0
Alarm max.:
Maximum probe S1 alarm threshold (valve 2)
9.3
Barg/pisg -20.0...200.0
Eic15
Alarm:
Enable probe S2 alarm (valve 2)
EN.
EN./DIS.
Type:
Type of probe S2 (valve 2)
CAREL NTC
CAREL NTC / 0-10V EXT. SI-
GNAL / NTC SPKP**T0 / CAREL
NTC-HT
Alarm min.:
Minimum probe S2 alarm threshold (valve 2)
-50.0
°C/°F
-60.0...200.0
Alarm max.:
Maximum probe S2 alarm threshold (valve 2)
105.0
°C/°F
-60.0...200.0
Eic16
Alarm:
Enable probe S3 alarm (valve 2)
EN.
EN./DIS.
Type:
Type of probe S3 (valve 2)
4-20mA
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Min.:
Minimum probe S3 reading (valve 2)
-1.0
Barg/pisg -20.0...200.0
Max.:
Maximum probe S3 reading (valve 2)
30.0
Barg/pisg -20.0...200.0
Alarm min.:
Minimum probe S3 alarm threshold (valve 2)
-1.0
Barg/pisg -20.0...200.0
Alarm max.:
Maximum probe S3 alarm threshold (valve 2)
30.0
Barg/pisg -20.0...200.0
Eic17
Alarm:
Enable probe S4 alarm (valve 2)
EN.
EN./DIS.
Type:
Type of probe S4 (valve 2)
CAREL NTC
CAREL NTC / NTC SPKP**T0 /
CAREL NTC-HT
Alarm min.:
Minimum probe S4 alarm threshold (valve 2)
-50.0
°C/°F
-60.0...200.0
Alarm max.:
Maximum probe S4 alarm threshold (valve 2)
105.0
°C/°F
-60.0...200.0
Eic18
ID1 confi guration:
Confi guration of action of digital input 1 on driver (valve 2)
REG. BACKUP
DISABLED / REG. SAFETY / REG.
BACKUP / START/STOP REG. /
VALVE FORCED 100% OPEN /
BATTERY ALARM MNG. / VALVE
REGULATION OPT. AFTER
DEFROST
ID2 confi guration:
Confi guration of action of digital input 2 on driver (valve 2)
DISABLED
DISABLED / REG. SAFETY / REG.
BACKUP / START/STOP REG. /
VALVE FORCED 100% OPEN /
BATTERY ALARM MNG. / VALVE
REGULATION OPT. AFTER
DEFROST
Eic19
DI1:
Digital input 1 status (valve 2)
---
DI2:
Digital input 2 status (valve 2)
---
Eic20
Valve A relay confi g.:
Confi guration of digital output1 (valve 2)
ALARM RELAY
DISABLED / ALARM RELAY
/ SOLENOID VALVE RELAY /
VALVE + ALARM RELAY / RE-
VERSED ALARM RELAY / VALVE
POSITION RELAY
Eic21
Valve B relay confi g.:
Confi guration of digital output 2 (valve 2)
ALARM RELAY
DISABLED / ALARM RELAY
/ SOLENOID VALVE RELAY /
VALVE + ALARM RELAY / RE-
VERSED ALARM RELAY / VALVE
POSITION RELAY
Eid02
Valve A opening at
start-up
Valve opening at start of control (valve 1)
50
%
0…100
Eid04
Valve A opened in
stand-by
Enable valve opening with control not active (valve 1)
NO
NO/YES
Start-up delay after
defrost
Start control delay after defrost (valve 1)
10
min
0…60
Valve A preposit. delay
Stationary time when valve pre-positions (valve 1)
6
s
0…18000