Code
Description
Arg 1
Arg 2
Arg 3
Arg 4
Config
Lock
If Config Lock = Yes, an active configuration lock in the Scanner prevents changes to the register.
700000 Loads factory defaults
for all configurations
except network
settings.
—
—
—
—
Yes
700001 Loads factory
defaults for all
configurations except
network settings and
communication port
settings
—
—
—
—
Yes
700070 Resets all grand
totals
—
—
—
—
No
700071 Resets flow run grand
totals
0 = All
1 = Flow Run 1
2 = Flow Run 2
—
—
—
No
700072 Resets pulse input
grand totals
0 = All
1 = Pulse Input 1
2 = Pulse Input 2
3 = Pulse Input 3
—
—
—
No
777333 Tests the control
code and returns a
response code of
“33337777.”
—
—
—
—
Yes
800000 Restarts all or
selected Scanner
Logic tasks.
0 = All
1 = Task 1
2 = Task 2
3 = Task 3
4 = Task 4
—
—
—
No
800001 Aborts all Scanner
Logic tasks and
enters abort state.
Emergency stop.
—
—
—
—
No
800008 Clears the
unacknowledged
Scanner Logic alarms
register. Does not
unlatch DIO.
—
—
—
—
No
Changing a Linear Calibration Factor
To update the linear calibration factor, write the register in following order:
1. Write the Nominal Factor value for the desired calibration in 32-bit floating point format:
– Pulse Input 1: Calibration: Nominal K-Factor, Address 8212
– Pulse Input 2: Calibration: Nominal K-Factor, Address 8213
– Pulse Input 3: Calibration: Nominal K-Factor, Address 8214
– Flow Run 1: Calibration: Nominal Factor, Address 8318
– Flow Run 2: Calibration: Nominal Factor, Address 8418
16
Section 1
Scanner 3100 Modbus Protocol