Code
Description
Arg
1
Arg
2
Arg
3
Arg
4
Config
Lock
If Config Lock = Yes, an active configuration lock in the Scanner prevents changes to the register.
601002 Programs the
operating mode for
a PID Controller to
automatic and sets an
override value. The
target analog output
must be in PID mode
for this command to
take effect.
1 = Analog Output 1
2 = Analog Output 2
Setpoint: 32-bit
floating point value in
the user-selected unit
for the measurement
category of the control
variable.
For example:
To apply a 123.45 set
point, convert 123.45
to a 32-bit floating
point (0x42f6e666),
write the value to
Argument 2, and write
command.
—
—
No
122
Section 2
Scanner 3100 Modbus Protocol