1. Convert the decimal format into binary format.
decimal format = 33
binary format = 32b 0000 0000 0000 0000 0000 0000 0010 0001
2. Refer to the
to decode the status information. In this example, PAR and INA are
active status.
Enron Event Record Format
Parameter
Data Type
Status
INT32
Address
INT32
Time (HHMMSS)
FP
Date (MMDDYY)
FP
As-Found
FP
As-Left
FP
The status parameter in the event record can be decoded with the following table:
Alarm Decoding
Description
Bit
<Unassigned>
0-8
User Change/Event
9
Low Low Alarm
10
Low Alarm
11
Hi Alarm
12
Hi Hi Alarm
13
<Unassigned>
14
Alarm Set/Reset (1 = Set, 0 = Reset)
15
Log Capacity (Scanner 3100)
Log Type
Device Capacity
Enron Capacity
Interval Logs
24576 to 6144*
1024
Daily Logs
2048
512
Event Logs
98304
4096
* Varies with configuration of log record size
Log Capacity (Slave Device)
Log Type
Device Capacity
Enron Capacity
Interval Logs
12288
1024
Daily Logs
1024
512
As-Found/As-Left Value Types
Value Type
Description
Unused
Floating point 0.0
User ID
User Index Number in floating point format
Alarm Value
Floating point representation of a register of any data type
Object Index
Floating point index number of the object index (ie: Gas Stream 4 = 4)
Slave Index
Floating point index number of the slave device
91
Scanner 3100 Modbus Protocol
Section 1