Slave 11 Configuration (Floating Points)
Register
(Decimal)
Register
(Hex)
Description
Data
Type
Units
Access
7501
1D4D
Slave Device 11: Flow Run Config: Atmospheric
Pressure
FP
psia
RW
7503
1D4F
Slave Device 11: Flow Run Config: Carbon Dioxide
FP
—
RW
7505
1D51
Slave Device 11: Flow Run Config: Nitrogen
FP
—
RW
7507
1D53
Slave Device 11: Flow Run Config: Specific Gravity
FP
—
RW
7509
1D55
Slave Device 11: Flow Run Config: Heating Value
FP
MMBtu/ft³
RW
7511
1D57
Slave Device 11: Flow Run Config: Oil Density
FP
lbm/ft³
RW
7513
1D59
Slave Device 11: Flow Run Config: Gas Fraction
FP
—
RW
7515
1D5B
Slave Device 11: Flow Run Config: Plate Diameter
FP
inch
RW
7517
1D5D
Slave Device 11: Flow Run Config: Pipe Diameter
FP
inch
RW
7519
1D5F
Slave Device 11: Flow Run Config: Cone Beta
FP
—
RW
7521
1D61
Slave Device 11: Flow Run Config: Nominal Value
FP
—
RW
7523
1D63
Slave Device 11: TFM Config: T1 Nominal Factor
FP
pulses/gal
RW
7525
1D65
Slave Device 11: TFM Config: T2 Nominal Factor
FP
pulses/gal
RW
Slave 12 Configuration (Floating Points)
Register
(Decimal)
Register
(Hex)
Description
Data
Type
Units
Access
7551
1D7F
Slave Device 12: Flow Run Config: Atmospheric
Pressure
FP
psia
RW
7553
1D81
Slave Device 12: Flow Run Config: Carbon Dioxide
FP
—
RW
7555
1D83
Slave Device 12: Flow Run Config: Nitrogen
FP
—
RW
7557
1D85
Slave Device 12: Flow Run Config: Specific Gravity
FP
—
RW
7559
1D87
Slave Device 12: Flow Run Config: Heating Value
FP
MMBtu/ft³
RW
7561
1D89
Slave Device 12: Flow Run Config: Oil Density
FP
lbm/ft³
RW
7563
1D8B
Slave Device 12: Flow Run Config: Gas Fraction
FP
—
RW
7565
1D8D
Slave Device 12: Flow Run Config: Plate Diameter
FP
inch
RW
7567
1D8F
Slave Device 12: Flow Run Config: Pipe Diameter
FP
inch
RW
7569
1D91
Slave Device 12: Flow Run Config: Cone Beta
FP
—
RW
7571
1D93
Slave Device 12: Flow Run Config: Nominal Value
FP
—
RW
7573
1D95
Slave Device 12: TFM Config: T1 Nominal Factor
FP
pulses/gal
RW
7575
1D97
Slave Device 12: TFM Config: T2 Nominal Factor
FP
pulses/gal
RW
Slave 13 Configuration (Floating Points)
Register
(Decimal)
Register
(Hex)
Description
Data
Type
Units
Access
7601
1DB1
Slave Device 13: Flow Run Config: Atmospheric
Pressure
FP
psia
RW
7603
1DB3
Slave Device 13: Flow Run Config: Carbon Dioxide
FP
—
RW
170