User and Programming Manual - Rev N
7.2.3 Distorted
Output
Table 7-4: Distorted Output
CAUSE
SOLUTION
Power source is grossly overloaded.
Reduce load.
The crest factor of the load exceeds 3:1.
Reduce load current peaks by reducing
load.
7.2.4 Unit Shuts Down After 3-5 Seconds
Table 7-5: Unit Shuts Down After 3-5 Seconds
CAUSE
SOLUTION
Output shorted.
Remove output short.
Output grossly overloaded.
Remove overload.
Operating load with too high inrush or start
up currents.
Consult factory for application advice.
7.2.5 No Output and No Lights on Front Panel
Table 7-6: No Output and No Lights on Front Panel
CAUSE
SOLUTION
Front panel power switched off.
Switch the breaker on.
No input power to the input connector.
Ensure correct input power.
Blown fuse.
Check fuse F1 and F2 on the DC power
supply and replace with same type and
rating. See Figure 7-2.
7.2.6 No Output but “Display” on Front Panel is On
Table 7-7: No Output But "Display" Is On
CAUSE
SOLUTION
“OUTPUT ON” switch is turned off.
Turn OUTPUT ON switch to “ON”.
Current limit programmed down or to zero.
Program current limit higher.
Voltage programmed down or to zero.
Turn amplitude control up.
Fault LED is lit.
Cycle Rear Panel power switch off and on.
54 April
2007
2001RP
Summary of Contents for 2001RP
Page 33: ...User and Programming Manual Rev N Figure 3 7 Test Setup 2001RP 24 April 2007 2001RP...
Page 47: ......
Page 60: ...User and Programming Manual Rev N Figure 6 3 Internal Adjustments 2001RP April 2007 51...
Page 65: ...User and Programming Manual Rev N Figure 7 1 Assembly Location 56 April 2007 2001RP...
Page 68: ...User and Programming Manual Rev N Figure 7 2 Replaceable Fuse Locations 2001RP April 2007 59...
Page 70: ...User and Programming Manual Rev N Figure 8 1 Rear Panel View 2001RP April 2007 61...
Page 90: ......