3 608 878 300
Tightening Technology |
Bosch Rexroth AG 481
System 350
| 3 608 878 300/2019-03
6.12.5.2
PLC interfaces
The IL function block provides a standard interface for access to PLUS functions of the tightening system
for the customer system PLC by means of Profinet I/O signals. The I/O signals are assigned to the
Profinet field bus interface via the PLC table or the
Data IL
function.
Profinet interface - Overview
For communication with the customer system PLC, the Profinet interface with a total of 64 bytes of input
and 64 bytes of output data is used. The various data ranges are configured in the
Set Profinet IO
interface
group.
Make the following settings on the
I/O and data
index card:
•
Number of I points
: 256E (32 bytes)
•
Number of O points:
448A (56 bytes)
•
Receive data:
0
•
Send data
: 0
•
Receive IL data
: 32
•
Send IL data
: 8
The signals in the input field (PLC outputs) are defined as follows:
The signals in the output field (PLC inputs) are defined as follows:
Table 6–159:
Signals in input field
Area
Address
Number of
bytes
Function
I points
Bytes 0-1
2
General bit signals, cell level
Bytes 2-5
4
Bypass signals for Ch 0.1 – Ch 4.5 (5 racks, 28 channels, 3 channels
reserve)
Bytes 6-7
2
(Reserve)
Bytes 8-11
4
Docking signals for Ch 0.1 – Ch 4.5 (5 racks, 28 channels, 3 channels
reserve)
Bytes 12-27
8*2
Application signals for FO1-8 (2 bytes per application block)
Bytes 28-31
4
(Reserve)
IL data
received
Bytes 32-51
20
ID code
Bytes 52-59
8*1
Position numbers (1 byte per application block)
Byte 60
1
Type number (type code)
Byte 61-63
3
(Reserve)
Table 6–160:
Signals in output field
Area
Address
Number of
bytes
Function
O points
Bytes 0-1
2
General bit signals, cell level
Bytes 2-5
4
Bypass acknowledgement for Ch 0.1 – Ch 4.5 (5 racks, 28 channels,
3 channels reserve)
Bytes 6-9
4
NOK signals for Ch 0.1 – Ch 4.5 (5 racks, 28 channels, 3 channels
reserve)
Bytes 10-13
4
OK signals for Ch 0.1 – Ch 4.5 (5 racks, 28 channels, 3 channels
reserve)
Bytes 14-17
4
NF signals for Ch 0.1 – Ch 4.5 (5 racks, 28 channels, 3 channels
reserve)
Bytes 18-21
4
Rdy signals for Ch 0.1 – Ch 4.5 (5 racks, 28 channels, 3 channels
reserve)
Bytes 22-25
4
Docking signals for Ch 0.1 – Ch 4.5 (5 racks, 28 channels, 3
channels reserve)
Bytes 26-41
8*2
Application acknowledgements for FO1-8 (2 bytes per application
block)
Bytes 42-55
14
(Reserve)
IL data
send
Bytes 56
20
Plus coupling error code
Bytes 57-63
7
(Reserve)
Summary of Contents for Rexroth Tightening System 350
Page 4: ...4 641 Bosch Rexroth AG Schraubtechnik System 350 3 608 878 300 2019 03 ...
Page 120: ...120 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...
Page 194: ...194 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...
Page 638: ...638 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...