Technical Data and Ordering Data
70
Bosch Rexroth AG
DOK-CONTRL-ILPSDO8****-AW04-EN-P
Rexroth Inline Module with Safe Digital Outputs R-IB IL 24 PSDO 8-PAC
11.3
Conformance with EMC Directive
Conformance with EMC Directive 2014/30/EU
Noise immunity test according to DIN EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2
(IEC 61000-4-2)
Criterion B
6 kV contact discharge, 8 kV air discharge
Electromagnetic fields
EN 61000-4-3
(IEC 61000-4-3)
Criterion A, field strength 10 V/m
Fast transients (burst)
EN 61000-4-4
(IEC 61000-4-4)
Criterion B, test voltage 2 kV
Surge voltage
EN 61000-4-5
(IEC 61000-4-5)
Test intensity 2, Criterion B
DC supply lines:
0.5 kV/0.5 kV (symmetrical/asymmetrical)
Signal lines:
1.0 kV/2.0 kV (symmetrical/asymmetrical)
Conducted interference
EN 61000-4-6
(IEC 61000-4-6)
Criterion A, test voltage 10 V
Noise emission test according to DIN EN 61000-6-4
Noise emission
EN 55011
Class A, industrial applications