Technical Data and Ordering Data
DOK-CONTRL-ILPSDO8****-AW04-EN-P
Bosch Rexroth AG
Rexroth Inline Module with Safe Digital Outputs R-IB IL 24 PSDO 8-PAC
Probability of a dangerous failure per hour for the entire mod-
ule (PFH)
SIL 2: 1% of 10
-6
, maximum (corresponds to 1 x 10
-8
)
SIL 3: 1% of 10
-7
, maximum (corresponds to 1 x 10
-9
)
Depends on the parameterization (see
Hardware fault tolerance (HFT) of the module
1
Permissible duration of use
20 years
Safety characteristic data according to EN 62061
Safety characteristic data according to EN ISO 13849-1
Achievable performance level
PL d (single-channel)
PL e (two-channel)
Depends on the parameterization and wiring (see
“Connection Options for Actuators Depending on the Param-
Diagnostic coverage (DC)
99%
Mean time to dangerous failure (MTTFd)
For single-channel assignment: 100 years
For two-channel assignment: 100 years
Supply voltage U
L
(logic)
The safety terminal is supplied with communications power via the bus coupler or a designated power terminal
in the station. The communications power is led in the Inline station via potential routing. For the technical data,
please refer to the data sheet for the bus coupler or power terminal used.
Current consumption
230 mA, maximum
Supply voltage U
M
(actuators)
The safety terminal is supplied with main voltage UM via the bus coupler or a power terminal in the station. The
main voltage is led in the Inline station via potential routing. For the technical data, please refer to the data sheet
for the bus coupler or power terminal used.
Nominal voltage
24 V DC according to EN 61131-2 and EN 60204
Tolerance
-15%/+20% including an entire AC voltage component with
peak value of 5%
Ripple
3.6 V
pp
Permissible voltage range
19.2 V DC to 30.0 V DC, including all tolerances, ripple in-
cluded
Current consumption
30 mA, typical (all outputs set) (plus actuator current)
Permissible interruption time
10 ms;
Within this time, the output voltage for the safe outputs fails as
the outputs are not internally buffered.
Surge protection
Yes (in the bus coupler/power terminal)
Protection against polarity reversal
Yes (in the bus coupler/power terminal)
Loss of the safety function when using unsuitable power supplies
Only use power supplies according to EN 50178/VDE 0160 (PELV).
WARNING
Module damage due to polarity reversal
Polarity reversal places a burden on the electronics and, despite protection against polarity reversal, can damage the mod-
ule. Therefore, polarity reversal must be prevented.
NOTICE