Digital inputs (safety technology L options)
The digital inputs correspond to IEC 61131, type 2.
Fig. 7-29:
Symbol
Data
Unit
Min.
Max.
Allowed input voltage
V
-3
30
High
V
11
30
Low
V
-3
5
Current consumption
1)
mA
7
15
1)
For KCU02, the specified values must be multiplied with the
number of zone nodes of the drive line.
Tab. 7-29:
Digital inputs (safety technology L options)
Bosch Rexroth AG
DOK-INDRV*-HCS01******-PR05-EN-P
220/341
Rexroth IndraDrive CsDrive Systems with HCS01
Technical data of the components