5
Condition as supplied, identification, transport and
storage
5.1
Condition as supplied
5.1.1
Factory testing
Voltage testing and insulation resistance testing
According to standard, the components of the Rexroth IndraDrive Cs range
are tested with voltage.
Testing
Test rate
Voltage testing
100% (EN 61800-5-1)
Insulation resistance testing
100% (EN 60204-1)
Tab. 5-1:
Applied standards
5.1.2
Customer testing
Risk of damage to the installed Rexroth com‐
ponents by customer-side testing of the ma‐
chine or installation!
NOTICE
Before conducting voltage testing or insulation resistance testing for an instal‐
lation or machine in which these components are used:
Disconnect all connections to the Rexroth components or disconnect the
plug-in connections to protect the electronic components.
DOK-INDRV*-HCS01******-PR05-EN-P
Bosch Rexroth AG
117/341
Rexroth IndraDrive CsDrive Systems with HCS01
Condition as supplied, identification, transport and storage