Components marked with gray background color: Option‐
al, depending on the application; the choke is used to re‐
duce current harmonics
A
Component HCS01 (all components A identical); connec‐
ted to supply mains via balancing chokes; interconnected
via DC bus
Bb
Bb relay contact wiring
M
Module bus (not obligatory)
Fig. 4-25:
Group Supply; all HCS01 Components Connected to Supply
Mains
Risk of fire caused by missing fuses!
NOTICE
Install a fuse before each drive controller. In case a short circuit occurs
in the drive controller, a fuse provides optimum safety against overheat‐
ing or fire (see also IEC 61800-5-1 and UL 508C).
For distribution in North America, single fuses are required for this type
of mains connection (see UL 508A).
In the scope of international and European standards (IEC/EN, not
North America), it is allowed to use a group fuse instead of the single
fuses. When selecting the nominal current of the group fuse, observe
the loop impedance, the line length and the line cross section of the
mains supply feeder (see IEC 60204-1, chapter Appendix A).
Observe the data for dimensioning line cross sections and fuses (see al‐
so IEC 60204-1, UL 508A and NFPA 79).
Parallel operationperation
Group supply or central supply allows the HCS01 components to be operated
in parallel to increase the DC bus continuous power.
Parallel operation of HCS01 components is only allowed under
the following conditions:
●
The components are of the same HCS01 range
●
The infeeding HCS01 components are of the same type
●
Additional chokes balance the mains current
Bosch Rexroth AG
DOK-INDRV*-HCS01******-PR05-EN-P
84/341
Rexroth IndraDrive CsDrive Systems with HCS01
Combining the individual components