Country of use: USA/Canada
Fuse I
N
Current carry‐
ing capacity I
Z
[A]
Cross section A
Installation type E
1 ×
2 ×
3 ×
4 ×
225
700
4 × 2/0 AWG
250
800
4 × 3/0 AWG
300
920
4 × 4/0 AWG
300
1020
4 × 250 kcmil
350
1140
4 × 300 kcmil
350
1240
4 × 350 kcmil
400
1340
4 × 400 kcmil
450
1520
4 × 500 kcmil
Tab. 11-4:
Line cross sections and fuses according to UL508A:2007, Table 28.1
Dimensioning variables of the table values
1. Ambient temperature T
A
of routed lines ≤ 40 °C
2. Temperature T
L
at conductor at nominal current: 90 °C for UL-listed
lines (USA/Canada) or 70 °C for PVC lines
3. The nominal current of the fuse is approx. 10-20% above the nominal
current I
LN
of the converter/supply unit or the determined current of the
drive system.
4. Installation types:
●
B1 in accordance with IEC 60364-5-52, e.g. stranded wires routed
in cable duct
●
B2 in accordance with IEC 60364-5-52, e.g. multi-core line routed
in cable duct
●
E in accordance with EN 60204-1, e.g. multi-core line routed on
open cable tray
●
In accordance with NFPA 79 (external wiring), UL508A (internal
wiring), NEC, NFPA 70:
–
1 cable with 3 conductors, 1 neutral conductor and 1 equip‐
ment grounding conductor
–
Routed in pipe on the wall
Internal wiring: Routing inside of control cabinet or inside of devi‐
ces
External wiring: Routing outside of control cabinet
Field wiring: Data of cross sections of terminal connectors wired by
the user (in the field)
5. Recommendation for design of the fuses:
●
International except for USA/Canada:
–
Fuse-link in accordance with IEC 60269-1, characteristic gG
(fuses)
–
Circuit breakers in accordance with IEC 60898-1/2, type B or
C
–
Circuit breakers in accordance with IEC 60947-2/6-2
DOK-INDRV*-HCS01******-PR05-EN-P
Bosch Rexroth AG
323/341
Rexroth IndraDrive CsDrive Systems with HCS01
Appendix