S2000R
S2000R-IP
47
www.bolid.ru
Figure 10-3
Testing
After mounting, the detector’s operations should be tested in accordance with one of the procedures
described below.
Simplified Test Procedure
Ensure the detector indicates that it is in Normal state;
Start testing quality of the link with the ARR32 by pressing the detector’s light guide for a
short time or by lighting the light guide by the laser beam;
Ensure the detector indicates the link quality procedure has been started (see Section 9);
Ensure that a Detector Test message has been delivered to the control and indicating
equipment;
Wait until the detector enters in Normal state.
Complete Test Procedure
Test quality of the link between the detector and the ARR32;
Ensure that the detector indicates its being in Normal state;
Blow a stream of hot air (from a hair dryer) with a temperature of 70
°
С
to 100
°
С
on to the
sensing element of the detector;
Ensure that the detector indicates its being in Fire Alarm state;
Ensure that the fire alarm has been delivered to the control and indicating equipment;
Wait until the detector enters in Normal state.
Prior to carrying out the complete testing procedure be sure that a fire alarm from the
detector will not start any announcement and/or fire extinguishing system