All your applicable local codes, standards, regulations, and ordinances.
The additional requirements below:
−
Do not install where the detector is directly above heating appliances, near vent
openings, or exposed to direct sunlight.
−
Make sure the detection area doesn’t have things which can waver (curtains, plants),
electric bulbs, glass or mesh partitions, or areas obscured by large things.
−
When the detector is armed, ensure all windows and balcony doors are closed and no
forced ventilation, calorifer, or air conditioner is on. There should be no animals or birds
within the premises.
−
Do not install directly above an entrance gate or entrance door.
Mounting
Mount the S2000R-IK to a flat vertical surface using two screws provided.
Testing Link Quality
The Link Quality Test procedure is designed to estimate stability of radio link between the detector
and the ARR32 at their current locations and when obstructions exist on the path of radio signals. You
are recommended to carry out the Link Quality Test before the devices are attached at their locations.
A Link Quality Test is started by a short press on the Prog button (see Figure 10-11). The procedure
takes 60 seconds, the detector indicating the results of the test as shown in Table 10-24.
As testing link quality is in progress you can move the detector and the ARR32 to find the best
locations for them.
You can also estimate quality of the link using S2000R Configurator as discussed in Section 7.
Testing
Just after mounting, the S2000R-IK should be tested for proper working condition.
Ensure the detector is in normal state in accordance with system indication.
Trigger the detector by walking through the detection area.
Ensure that the detector indicates the intruder alarm, and a relevant message is received by
control and indicating equipment.
Wait until the detector returns to normal state.