Addressable Radio Link System
www.bolid.ru
114
Problem
Solution
ARR32 Core firmware error
Description:
POWER, LOOP, and RADIO LEDs of the ARR32 shows solid
amber light.
Solution:
Update Core firmware of the ARR32 by means of S2000R
Configurator (see Section 7).
If S2000R Configurator is unable to connect the invalid ARR32,
contact technical support for assistance.
ARR32 Radio firmware error
Description:
POWER LED of the ARR32 illuminates with amber while LOOP
and RADIO flashes simultaneously twice per second.
Solution:
Update Radio firmware of the ARR32 by means of S2000R
Configurator (see Section 7).
WARNING: Make sure that the version of the firmware is
compatible with the current versions of firmware of the connected
radio link devices
ARR32
Core
firmware
updating failure
Description:
The ARR32 reboots itself at regular intervals and starts a
procedure of updating Core firmware. POWER LED shows solid
amber light, LOOP LED and RADIO LED flash alternately with
amber four times per second.
Solution:
Power off the ARR32 and connect it to a USB port of the PC using
the USB cable provided pressing and holding the program button
S2 (see Section 3). Run S2000R Configurator and update ARR32
Core firmware ARR32 (see Section 7).
WARNING: Make sure the version of firmware is compatible with
the version of the ARR32 PC board
Core/Radio link error
Description:
RADIO LED shows solid amber light.
Solution:
The device should be repaired by a qualified professional. Please
contact technical support.