Ensure that the call point indicates its being in Normal state;
Press the resettable element of the call point causing its mechanical part to kick in;
Ensure that the call point indicates its being in Fire Alarm state;
Ensure that the fire alarm has been delivered to the control and indicating equipment;
Using the supplied key, reset the call point and wait until the call point indicates its being in
Normal state.
Maintenance
While maintaining your fire alarm system, test the proper operation of the call point at least
every 3 months;
On receiving a low battery message for the main or backup battery replace both the
batteries.
Prior to testing the call point be sure that fire alarm triggered by this one will not activate
any announcement and/or fire extinguishing system