Addressable Radio Link System
www.bolid.ru
110
Getting Started
While stored the ASR2 is deactivated (in the sleep mode). To activate the ASR1, briefly set the
service magnet to the service contact. Successful activation is accompanied by start of light
indication.
After activation of the ASR1 the battery depassivation procedure runs.
The depassivation procedure activates batteries after long term storage and can take up to 5 minutes.
The process of depassivation is indicated as shown in Table 10-61. If depassivation fails contact the
supplier to replace the equipment.
Connecting and Programming
Connect the ASR1 to the ARR32 and set its parameters in the configuration of the polling loop
controller as discussed in Sections 6, 7, and 8 of this Manual.
To connect the ASR1 to the ARR32, switch the ARR32 to the Device Connecting mode and then set
the service magnet to the service contact of the ASR1 for a time more than 5 seconds.
Mounting Location Considerations
Considering the mounting location for the S2000R-ASR1, please follow all your applicable local
codes, standards and regulations and instructions from Section 9 of this Manual.
Testing Link Quality
The Link Quality Test procedure is designed to estimate stability of radio link between the S2000R-
ASR1 and the ARR32 at their current locations and when obstructions exist on the path of radio
signals. You are recommended to carry out the Link Quality Test before the devices are attached at
their locations.
The ASR1 should be activated strictly before starting operating the meter (prior to water
starting flowing through the meter)
The ASR1 should be programmed with Transmission Interval set to 15 seconds (in the
programming mode). For doing so run S2000R Configurator (see Section 7) and place the
service magnet to the meter housing from the side of the magnetic contact for a short time
(Figure 10-27).
The ASR2 quits the programming mode automatically on expire of 10 minutes since closing
Configurator.