Testing
After mounting, test the detector’s operations in accordance with one of the procedures described
below.
Simplified Test Procedure
Ensure the detector indicates that it is in Normal state;
Start testing quality of the link with the ARR32 by pressing the detector’s light guide for a
short time or by lighting the light guide by the laser beam;
Ensure the detector indicates that the link quality test procedure has been started (see
Section 9);
Ensure that a Detector Test message has been delivered to the control and indicating
equipment;
Wait until the detector enters in Normal state.
Complete Test Procedure
Test quality of the link between the detector and the ARR32;
Ensure that the detector indicates its being in Normal state;
Spray some smoke detector test aerosol into the smoke chamber of the detector;
Ensure that the detector indicates its being in Fire Alarm state;
Ensure that the fire alarm has been delivered to the control and indicating equipment;
Wait until the detector enters in Normal state.
Maintenance
At least annually inspect the screen assembly under the detector cover. If there is any dust
on the screen assembly, clean this one with a vacuum cleaner (by pumping air).
When a Service Required message is received from the detector remove the dust from the
sensing chamber.
On receiving a low battery message for the main or backup battery replace both the
batteries.
Prior to carrying out the complete testing be sure that a fire alarm sent by the detector
will not start any announcement and/or fire extinguishing system
To avoid damage to the measurement equipment and the detector, use only the smoke
detector test aerosol or tester which is designed specifically for testing smoke detectors