S2000R
Appendix A. Batteries
87
www.bolid.ru
S2000R-RM REV.01
General
S2000R-RM Radio Link Relay Module rev.01 for 220 V (hereinafter
referred to as the module) is designed to control executive devices which
require 220 Vac.
The module features two relay outputs which are galvanically isolated
from each other and from the power supply circuits and which are
controlled over the radio link.
Each output is equipped with a fuse to protect the relevant control circuit
against overload and short-circuits.
The module is powered by mains power 220 Vac (the main power supply).
The module incorporates a lithium battery intended to be used for operations with the module when its
case is open (when being connected to the ARR32 and so on) and for sending messages in case of
mains power loss.
The module is designed to be used within closed areas and is not intended to operate in aggressive
media, dust conditions, or in explosion-hazardous premises.
The module is designed for round-the-clock operation.
Specifications
Table 10-41. S2000R-RM rev.01 Specifications
AC Power Voltage
90...264 V (rated voltage 220 V at 50 Hz)
Consumed Power
1 VA max
Outputs
2
Max Switched Voltage:
- for alternating current (cos
φ
> 0.90)
- for direct current
250 V
30 V
The outputs are controlled only if the module is powered by 220 V mains. The outputs
are shut off when mains power fails or is not available.
The electric circuits of the modules are not galvanically isolated from the power input and
are under dangerous voltage in normal operation. All works with the module (excluding