7 Main Menu Device Setup
LB 470RID Level
132
56925-1BA2 Rev.02, 05/2021
2.
Confirm the value with the Enter key.
The time constant has been changed.
Signal Condition: PV Range
Device Setup | Setup | Signal Condition | PV Range
The lower and upper limit of the process range of the active measuring parameter
set can be set in the tab “PV Range” (Process Value Range). These limits define the
signal range of the analog current output (4 ... 20 mA or 0 ... 20 mA). The unit is
displayed that is selected in the menu
System | Units
in the box "PV".
1
2
Input field lower range value [%]
Input field upper range value [%]
Fig. 105 Signal Condition (PV Range)
1.
Click on the input field (Fig. 105, item 1) to enter, in percent [%], the level
which should correspond to an output current of e.g. 4 mA.
2.
Confirm with the Enter key.
3.
Click on the input field (Fig. 105, item 2) to enter, in percent [%], the level
which should correspond to an output current of 20 mA.
4.
Confirm with the Enter key.
The PV values are set.