LB 470RID Level
7 Main Menu Device Setup
56925-1BA2 Rev.02, 05/2021
131
7.3.5
Signal Condition
Device Setup | Setup | Signal Condition
You can perform the following settings and read information in the “Signal Con-
dition” submenu:
•
Damping (time constant)
•
PV range
•
Rapid Switch
•
XIP (X-Ray interference protection)
•
RID
•
Source Replacement
Fig. 103 Menu ”Signal Condition”
Signal Condition: Damping
Device Setup | Setup | Signal Condition | Damping
The reaction time of the measured value display (standard display) can be set in
the window “Damping”. The measurement reacts quickly to rapid process changes
(e.g. by agitators) for a small time constant (min. 1 sec). The measurement reacts
correspondingly slower for a larger time constant. However, due to the stronger
filtering, the statistical error is reduced with a larger time constant and the meas-
urement is correspondingly less noisy. A typical time constant for radiometric level
measurements is 20 seconds.
Fig. 104 Signal Condition (damping)
1.
Click on the input field to change the time constant.